Final | 11/19/2001 | 11/20/2001 | 11/20/2001 | A | PASS |
Mike Kinnear
|
|
|
###-#### DAN ok final 11/20/2001 11:06:19 AM
|
Final | 10/9/2001 | 10/11/2001 | 10/11/2001 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/09/2001 at 16:24:03. Contact: ###-####. temp occupancy 1st floor corridors 10/11/2001 10:42:15 AM
|
Final | 10/9/2001 | 10/10/2001 | 10/10/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 10/09/2001 at 16:23:21. Contact: ###-####. ok part final 2nd floor coridor correction nec 110-3(b) roof exhaust fan 10/10/2001 10:06:20 AM
|
Final | 10/3/2001 | 10/4/2001 | 10/4/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 10/03/2001 at 17:07:00. Contact: ###-####. part final rooms ok 1st floor 10/4/2001 9:32:49 AM
|
Final | 9/28/2001 | 10/2/2001 | 10/2/2001 | A | PART |
Mike Kinnear
|
|
|
###-#### DAN part final 2nd floor rooms 10/2/2001 12:59:28 PM
|
Electrical Rough-In | 9/25/2001 | 9/26/2001 | 9/26/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 09/25/2001 at 19:03:22. Contact: ###-####. ok cover ceilings corridors 1st level areas 3,4,5,6,7,&8 9/26/2001 9:45:27 AM
|
Electrical Rough-In | 9/12/2001 | 9/13/2001 | 9/13/2001 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 09/12/2001 at 17:22:33. Contact: ###-####. ok ceilings 9/14/2001 12:11:44 PM
|
Electrical Rough-In | 8/31/2001 | 8/31/2001 | 8/31/2001 | P | PART |
Mike Kinnear
|
|
|
Added by Inspector: 412 On 8/31/2001 3:17:34 PM ok cover canopy area #5
|
Electrical Rough-In | 7/28/2001 | 7/30/2001 | 7/30/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 07/28/2001 at 08:38:09. Contact: ###-####. ok cover ceiling 2nd floor area #4 7/30/2001 8:46:28 AM
|
Electrical Rough-In | 7/24/2001 | 7/25/2001 | 7/25/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 07/24/2001 at 17:12:05. Contact: ###-####. ok cover cor. 1st floor area 3 & 4 7/25/2001 8:48:03 AM
|
Electrical Rough-In | 7/18/2001 | 7/19/2001 | 7/19/2001 | P | PART |
Mike Kinnear
|
|
|
###-#### part ok cover area 6 lower ceiling area 3 2nd floor walls area 4 1st floor ceiling 7/19/2001 3:04:18 PM
|
Electrical Rough-In | 7/13/2001 | 7/16/2001 | 7/16/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 07/13/2001 at 11:36:44. Contact: ###-####. ok cover area 3 2nd floor walls 7/16/2001 9:14:49 AM
|
Electrical Rough-In | 7/9/2001 | 7/9/2001 | 7/9/2001 | A | PART |
Mike Kinnear
|
|
|
Added by Inspector: 412 On 7/9/2001 11:40:38 AM conf on clearances in generator dog houses with micro john davis
|
Rough-In Permanent Service | 6/29/2001 | 7/2/2001 | 7/2/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/29/2001 at 16:42:50. Contact: ###-####. ok turn on main service 7/2/2001 8:22:59 AM
|
Rough-In Permanent Service | 6/29/2001 | 6/29/2001 | 6/29/2001 | A | CANC |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/29/2001 at 06:53:09. Contact: ###-####. canc. by contractor 6/29/2001 8:29:06 AM
|
Electrical Rough-In | 6/27/2001 | 6/27/2001 | 6/27/2001 | P | PART |
Mike Kinnear
|
|
|
Dan ###-#### 2nd floor area 3 floor ok cover floor & area 4 stairwell ok cover walls & west canopy part cover ceiling 6/27/2001 4:28:40 PM
|
Electrical Rough-In | 6/25/2001 | 6/25/2001 | 6/25/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/25/2001 at 06:58:11. Contact: ###-####. ok cover 2nd floor area 6 ceiling area 3 & 4 corridor floor 6/25/2001 11:17:13 AM
|
Electrical Rough-In | 6/20/2001 | 6/21/2001 | 6/21/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/20/2001 at 18:16:12. Contact: ###-####. ok cover walls 1st floor area 3 6/21/2001 9:34:17 AM
|
Rough-In Permanent Service | 6/19/2001 | 6/20/2001 | 6/20/2001 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/19/2001 at 16:55:47. Contact: ###-####. ok cover ceiling 2nd floor area 5 6/20/2001 2:29:16 PM
|
Electrical Rough-In | 6/12/2001 | 6/12/2001 | 6/12/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/12/2001 at 07:01:45. Contact: ###-####. ok cover north wall aera1/2 1st floor ok cover mech rm wall area 3 1st floor ok cover walls break rm area 7 2nd floor ok cover floor elect rm area 4 2nd floor 6/12/2001 11:25:47 AM
|
Electrical Rough-In | 6/6/2001 | 6/7/2001 | 6/7/2001 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/06/2001 at 07:39:39. Contact: ###-####. ok cover ceiling 1st floor area #6 ok cover walls 2nd floor area#4 6/7/2001 3:37:55 PM
|
Electrical Rough-In | 6/4/2001 | 6/4/2001 | 6/4/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/04/2001 at 07:03:44. Contact: ###-####. ok cover walls area 4 1st floor 6/4/2001 9:33:45 AM
|
Electrical Rough-In | 5/31/2001 | 5/31/2001 | 5/31/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 05/31/2001 at 07:03:54. Contact: ###-####. ok cover south canapy ceiling UL came and ok transformers for 6 inch clearances 5/31/2001 3:20:37 PM
|
Electrical Rough-In | 5/23/2001 | 5/23/2001 | 5/23/2001 | P | PASS |
Mike Kinnear
|
|
|
Added by Inspector: 412 On 5/23/2001 1:28:21 PM conf with contractor
|
Electrical Rough-In | 5/21/2001 | 5/22/2001 | 5/22/2001 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 05/21/2001 at 17:21:49. Contact: ###-####. ok cover 1st floor area7 & 5 ceiling 2nd floor are 4 floor area 3 shaft walls & bathrms 5/22/2001 4:04:06 PM
|
Electrical Rough-In | 5/17/2001 | 5/18/2001 | 5/18/2001 | P | PART |
Mike Kinnear
|
|
|
Dan ###-#### ok cover ceiling area 8 2nd floor ok cover bathrms 1st floor ok cover ent. at basement 5/18/2001 10:22:00 AM
|
Electrical Rough-In | 5/15/2001 | 5/15/2001 | 5/15/2001 | P | PART |
Mike Kinnear
|
|
|
###-#### ok cover 2nd floor area 6 walls & 1st floor area 8 jim storey okayed strapping relock cable to ceiling grid system 5/15/2001 2:23:44 PM
|
Electrical Rough-In | 5/11/2001 | 5/14/2001 | 5/14/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 05/11/2001 at 14:24:19. Contact: ###-####. ok cover floor area 4 1st floor 5/14/2001 10:40:04 AM
|
Electrical Rough-In | 5/10/2001 | 5/10/2001 | 5/10/2001 | P | PASS |
Mike Kinnear
|
|
|
mic #36 Dan ###-#### conf regarding ceiling there is to be NO ceiling tile installed without ok to cover 5/10/2001 3:11:56 PM
|
Electrical Rough-In | 5/7/2001 | 5/8/2001 | 5/8/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 05/07/2001 at 16:44:51. Contact: ###-####. ok cover int. walls area #5 5/8/2001 11:44:48 AM
|
Electrical Rough-In | 4/30/2001 | 4/30/2001 | 4/30/2001 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 04/30/2001 at 07:32:51. Contact: ###-####. ok cover inter. walls area #6 1st floor & walls basement 4/30/2001 3:16:48 PM
|
Electrical Rough-In | 4/24/2001 | 4/24/2001 | 4/24/2001 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 04/24/2001 at 07:53:08. Contact: ###-####. ok cover floor area 5 & 6 ok cover walls area 5 & 6 comm rm & elect rm 4/24/2001 3:10:32 PM
|
Electrical Rough-In | 4/19/2001 | 4/19/2001 | 4/19/2001 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 04/19/2001 at 06:52:44. Contact: ###-####. ok cover walls 1st floor area 3 & 5 4/19/2001 3:14:55 PM
|
Electrical Rough-In | 4/16/2001 | 4/16/2001 | 4/16/2001 | P | PART |
Mike Kinnear
|
|
|
###-#### ok cover ext & corridor walls area 3& 4 1st & 2nd floor 4/16/2001 3:25:32 PM
|
Electrical Rough-In | 4/10/2001 | 4/11/2001 | 4/11/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 04/10/2001 at 12:44:31. Contact: ###-####. ok cover floor 1st floor area 6 ok cover walls 2nd floor ares 7 & 8 4/11/2001 9:45:32 AM
|
Electrical Rough-In | 4/3/2001 | 4/3/2001 | 4/3/2001 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 04/03/2001 at 07:40:20. Contact: ###-####. riser rm east 1st floor ok cover walls south stair well 2nd floor ok cover walls 1st floor area 5 ok cover floor 4/3/2001 2:18:08 PM
|
Electrical Rough-In | 3/26/2001 | 3/27/2001 | 3/27/2001 | P | PART |
Mike Kinnear
|
|
|
###-#### 1st level area 8 int. walls 1st level area 5 firealarm rm walls1st level area 8 floor cover coridor 2nd floor area 7 bathrm walls 2nd floor area 5 electrm walls 3/27/2001 3:24:24 PM
|
Electrical Rough-In | 3/22/2001 | 3/22/2001 | 3/22/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 03/22/2001 at 07:05:14. Contact: ok cover int walls area 7 - 1st floor ok floor 2nd floor area 8 shaft 2nd floor area 8 ok cover 3/22/2001 11:56:13 AM
|
Electrical Rough-In | 3/20/2001 | 3/20/2001 | 3/20/2001 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 03/20/2001 at 09:08:30. Contact: ###-####. ok cover part c print for area 3/20/2001 5:30:35 PM
|
Electrical Rough-In | 3/14/2001 | 3/15/2001 | 3/15/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 03/14/2001 at 18:00:10. Contact: ###-####. ok cover walls 2nd floor area 5 & 6 prem. & corador 3/15/2001 2:44:23 PM
|
Electrical Rough-In | 3/7/2001 | 3/7/2001 | 3/7/2001 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 03/07/2001 at 08:38:52. Contact: ###-####. ok cover walls cord. & prem area 5 & 6 1st floor 3/7/2001 1:57:45 PM
|
Electrical Rough-In | 2/28/2001 | 2/28/2001 | 2/28/2001 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 02/28/2001 at 08:46:14. Contact: ###-####. ok cover walls 1st & 2nd floor see prints area 7 & 8 2/28/2001 3:42:14 PM
|
Electrical Rough-In | 2/19/2001 | 2/20/2001 | 2/20/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 02/19/2001 at 09:52:08. Contact: ###-####. ok inter walls area 7 1st floor & ok cover ext 2nd floor area 7 & 8 2/20/2001 12:53:14 PM
|
Electrical Rough-In | 2/13/2001 | 2/14/2001 | 2/14/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 02/13/2001 at 18:06:43. Contact: ###-####. ok cover int walls area 7 2/14/2001 2:36:43 PM
|
Electrical Rough-In | 2/6/2001 | 2/7/2001 | 2/7/2001 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 02/06/2001 at 13:11:22. Contact: ###-####. ok cover ext walls east half of first floor 2/7/2001 11:44:01 AM
|