Final | 5/7/2003 | 5/7/2003 | 5/7/2003 | P | PASS |
Pat Lass
|
|
|
###-####
|
Final | 5/1/2003 | 5/5/2003 | 5/5/2003 | P | FAIL |
Pat Lass
|
|
|
###-#### stephen
210.8 $42 reinspection fee due correction not made. 5/5/2003 1:54:39 PM 5/5/2003 1:56:04 PM
|
Electrical Rough-In | 2/25/2003 | 2/26/2003 | 2/26/2003 | A | NH |
Jack Frank
|
|
|
steve ###-#### notice posted called 2/26/2003 9:46:46 AM
|
Electrical Rough-In | 2/26/2003 | 2/26/2003 | 2/26/2003 | P | FAIL |
Pat Lass
|
|
|
###-#### steve
corrections not made open box no covers 2/26/2003 4:31:32 PM
|
Electrical Rough-In | 2/11/2003 | 2/12/2003 | 2/12/2003 | A | NH |
Tim McCullough
|
|
|
###-#### CELL ###-####
no /acc.left card 2/12/2003 10:04:56 AM 2/12/2003 10:05:20 AM
|
Final | 1/15/2003 | 1/15/2003 | 1/15/2003 | P | FAIL |
Pat Lass
|
|
|
steven-- ###-#### or cell ###-####-received postcard--call 1st before insp Changed status from expired to issue per Jim Schmer
422.31 Disconnection of Permanently Connected Appliances.
Water heater requires a disconnect within sight or lock out on breaker.
210.52 Dwelling Unit Receptacle Outlets.
(B) Small Appliances.
(3) Kitchen Receptacle Requirements. Receptacles installed in a kitchen to serve countertop surfaces shall be supplied by not fewer than two small-appliance branch circuits,
210.8 Ground-Fault Circuit-Interrupter Protection for Personnel.
(A) Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in (1) through (8) shall have ground-fault circuit-interrupter protection for personnel.
(1) Bathrooms
1/15/2003 3:18:57 PM
|
Final | 1/15/2003 | 1/15/2003 | 1/15/2003 | P | FAIL |
Pat Lass
|
|
|
steven-- ###-#### or cell ###-####-received postcard--call 1st before insp
422.31 Disconnection of Permanently Connected Appliances.
Water heater requires a disconnect within sight or lock out on breaker.
210.52 Dwelling Unit Receptacle Outlets.
(B) Small Appliances.
(3) Kitchen Receptacle Requirements. Receptacles installed in a kitchen to serve countertop surfaces shall be supplied by not fewer than two small-appliance branch circuits,
210.8 Ground-Fault Circuit-Interrupter Protection for Personnel.
(A) Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in (1) through (8) shall have ground-fault circuit-interrupter protection for personnel.
(1) Bathrooms
1/15/2003 2:05:35 PM
|
Electrical Rough-In | 11/20/2001 | 11/23/2001 | 11/23/2001 | A | PASS |
Marv Burrus
|
|
|
###-####. remodel r/i. ok 11/23/2001 10:49:33 AM
|
Electrical Rough-In | 10/31/2001 | 11/1/2001 | 11/1/2001 | A | PASS |
Marv Burrus
|
|
|
###-#### STEVEN . conference: branch circuits requirements in kitchen remodel. 11/1/2001 11:35:22 AM
|
Electrical Rough-In | 9/13/2001 | 9/14/2001 | 9/14/2001 | A | PASS |
Marv Burrus
|
|
|
###-####. conference; service installation. 9/14/2001 10:11:12 AM
|
ELE-Aging Inspection | 8/31/2001 | 8/31/2001 | 8/31/2001 | | NR |
Marv Burrus
|
|
|
no inspections requested 8/31/2001 10:00:45 AM
|
ELE-Aging Inspection | 6/1/2001 | 6/1/2001 | 6/1/2001 | | PASS |
Marv Burrus
|
|
|
no action. 6/1/2001 10:27:53 AM
|