Final | 9/10/2001 | 9/10/2001 | 9/10/2001 | P | PASS |
Marv Burrus
|
|
|
###-####. completed. 9/10/2001 1:56:40 PM
|
Electrical Rough-In | 8/3/2001 | 8/6/2001 | 8/6/2001 | A | PART |
Marv Burrus
|
|
|
uffer ground--andy ###-####. ok for concrete pour. 8/6/2001 9:00:34 AM
|
Rough-In Permanent Service | 8/1/2001 | 8/2/2001 | 8/2/2001 | A | PART |
Marv Burrus
|
|
|
reinspection ###-#### . ele r/i only; u-fer not correct. 8/2/2001 11:59:15 AM
|
Rough-In Permanent Service | 7/30/2001 | 7/30/2001 | 7/30/2001 | P | FAIL |
Jim Schmer
|
|
|
###-#### 1-nail plts, 2-cond. 1 1/4" from stud face, 3-cond. term in box, 4-cond. secured individually at panel, 5-no u-fer, 6-panel not app. as raceway 7/30/2001 1:03:17 PM
|