Final | 9/21/2001 | 9/21/2001 | 9/21/2001 | P | PASS |
Marv Burrus
|
|
|
###-####. tenant improvement northend space. completed. 9/21/2001 1:55:40 PM
|
Electrical Rough-In | 8/28/2001 | 8/29/2001 | 8/29/2001 | A | PASS |
Marv Burrus
|
|
|
###-####. corrections completed; r/i ok. service not completed. 8/29/2001 8:46:26 AM
|
Electrical Rough-In | 8/27/2001 | 8/28/2001 | 8/28/2001 | A | FAIL |
Marv Burrus
|
|
|
###-#### ED. 110-12: openings shall be closed. 331-11: pvc shall be suppoted at 3ft of cabined. 350-18 flex conduit shall be supported at intervals of no more than 41/2 ft
corrections posted. 8/28/2001 12:02:57 PM
|