Final | 11/7/2001 | 11/8/2001 | 11/8/2001 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/07/2001 at 16:23:16. Contact: ###-####. ok 11/8/2001 11:29:10 AM
|
Final | 11/7/2001 | 11/7/2001 | 11/7/2001 | P | NR |
Jack Frank
|
|
|
###-#### JUDITH ceiling cover ok needs 370-20 needs box extensions where boxes are not flush with combustible material called 11/7/2001 5:25:59 PM
|
Electrical Rough-In | 10/16/2001 | 10/17/2001 | 10/17/2001 | A | PART |
Jack Frank
|
|
|
partial\###-#### hard ceiling ok 10/17/2001 11:01:58 AM
|
Electrical Rough-In | 10/11/2001 | 10/12/2001 | 10/12/2001 | A | PART |
Jack Frank
|
|
|
partial r/i judith ###-#### over 360 degrees of bends corrected in feed to sub panel r/i ok 10/12/2001 2:02:28 PM
|
Rough-In Permanent Service | 10/9/2001 | 10/10/2001 | 10/10/2001 | P | PART |
Jack Frank
|
|
|
partial r/i & ser- judith ###-#### r/i ok no power over 360 degrees of bends in 2 inch emt that feeds sub panel called
10/10/2001 4:41:45 PM
|
Electrical Rough-In | 10/3/2001 | 10/4/2001 | 10/4/2001 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/03/2001 at 11:42:36. Contact: ###-####. u/g ok 10/4/2001 10:24:58 AM
|
Final | 11/6/2001 | 11/7/2001 | 3/6/2000 | A | NR |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/06/2001 at 12:26:47. Contact: ###-####. not ready conference ok shall support wiring above grid ceiling 11/6/2001 5:55:32 PM
|