Final | 1/13/2003 | 1/13/2003 | 1/13/2003 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 01/13/2003 at 09:52:27. Contact: ###-####. ok cor. made 1/13/2003 2:09:36 PM
|
ELE-Aging Inspection | 12/11/2002 | 12/11/2002 | 12/11/2002 | | PART |
Jack Frank
|
|
|
stopped at job site they need to install #8 equipment grd for voltage drop 20 amp circuit with #8 phase and neutral 250.122(B) called Leon at Tri state he will check it out and get back with me and call for final 12/11/2002 6:45:34 PM
|
ELE-Aging Inspection | 12/31/2001 | 12/31/2001 | 12/31/2001 | | PART |
Jack Frank
|
|
|
stopprd by job site W S U C 1/2/2002 12:42:37 PM
|
Electrical Rough-In | 10/30/2001 | 10/31/2001 | 10/31/2001 | A | PASS |
Jim Schmer
|
|
|
###-#### chris underground for parking lot, except pole lites - jms 10/30/2001 12:45:35 PM
|
Electrical Rough-In | 10/29/2001 | 10/29/2001 | 10/29/2001 | P | PART |
Jack Frank
|
|
|
###-#### chris u/g ok for under street they will call when parking lot later 10/29/2001 2:56:02 PM
|