Final | 12/5/2001 | 12/6/2001 | 12/6/2001 | P | PASS |
Joe Ray
|
|
|
###-#### billy joe
|
Final | 12/4/2001 | 12/5/2001 | 12/5/2001 | A | FAIL |
Marv Burrus
|
|
|
###-#### BILLY JOE. no access; called contractor to reschedule. 12/5/2001 9:37:20 AM
|
Electrical Rough-In | 11/2/2001 | 11/5/2001 | 11/5/2001 | A | FAIL |
Marv Burrus
|
|
|
###-#### MARTIN . no access; called contractor to reschedule. 11/5/2001 10:32:53 AM
|
Electrical Rough-In | 11/5/2001 | 11/5/2001 | 11/5/2001 | P | PASS |
Marv Burrus
|
|
|
###-#### ron. corrections completed, ok.,. 11/5/2001 11:24:59 AM
|
Electrical Rough-In | 11/2/2001 | 11/2/2001 | 11/2/2001 | P | FAIL |
Jack Frank
|
|
|
###-#### MARTIN do not cover , correction, and $42.00 fee due posted called 300-4 nail plates and 1 1/4, and 336-18 shall not staple cables on edge 11/2/2001 2:06:38 PM
|
Electrical Rough-In | 10/31/2001 | 11/1/2001 | 11/1/2001 | A | FAIL |
Jack Frank
|
|
|
###-#### corrections not made still needs nail plates and 1 1/4 inches for cables on studs called cor. posted 11/1/2001 1:53:27 PM
|
Electrical Rough-In | 10/29/2001 | 10/30/2001 | 10/30/2001 | A | FAIL |
Joe Ray
|
|
|
r/i- billie joe ###-#### 373-5-c too many cables in a conn./300-4 protection of wire 10/30/2001 10:40:12 AM
|