Final | 4/9/2002 | 4/10/2002 | 4/10/2002 | A | PASS |
Marv Burrus
|
|
|
CALL BILL THOMAS ###-#### FOR ACCESS
|
Rough-In Permanent Service | 3/6/2002 | 3/6/2002 | 3/6/2002 | P | PASS |
Marv Burrus
|
|
|
###-#### BILL KEY IS IN BOTTOM MAIN DISCONNECT. corrections completed.
p/s ug ne challenger ele #3858-ok
pump station. 3/6/2002 2:20:35 PM
|
Permanent Service | 3/1/2002 | 3/4/2002 | 3/4/2002 | A | FAIL |
Marv Burrus
|
|
|
###-#### BILL KEY AT BOTTOM OF MAIN DISCONNECT nec: 250. equiptment bonding, lock-nuts not approved for damp locations ufer ground chokes 110-26: cleareances in front of disconnect. discussed violations with contractor. idaho power connected to power before inspection. 3/4/2002 10:59:28 AM
|
Electrical Rough-In | 2/25/2002 | 2/28/2002 | 2/28/2002 | A | CANC |
Marv Burrus
|
|
|
###-####. contractors request, will reschedule 2/27/2002 4:20:09 PM
|
Electrical Rough-In | 12/27/2001 | 12/27/2001 | 12/27/2001 | P | PASS |
Marv Burrus
|
|
|
Scheduled by a contractor via Hello! on 12/27/2001 at 10:22:03. Contact: ###-####. p.v.c. conduit in decking ok for pour; 12/27/2001 3:51:03 PM
|
Permanent Service | 12/20/2001 | 12/21/2001 | 12/21/2001 | A | PASS |
Marv Burrus
|
|
|
UFER\###-#### UPPER LIFT STATION
|
Electrical Rough-In | 11/16/2001 | 11/16/2001 | 11/16/2001 | A | PART |
Marv Burrus
|
|
|
Added by Inspector: 403 On 11/16/2001 8:50:02 AM pvc conduit in decking of concrete pump station.
|