Final | 2/26/2002 | 2/26/2002 | 2/26/2002 | P | PASS |
Mike Kinnear
|
|
|
PHIL ###-#### ok final 2/26/2002 1:31:35 PM
|
Final | 2/25/2002 | 2/25/2002 | 2/25/2002 | P | FAIL |
Mike Kinnear
|
|
|
PHIL ###-#### nec 314.23(d)(2) all boxes shall be supported BCC no code violation shall be retained 2/25/2002 1:40:59 PM
|
Final | 2/21/2002 | 2/22/2002 | 2/22/2002 | A | FAIL |
Mike Kinnear
|
|
|
nathan-- ###-#### fn bcc all tiles installed they to remove tiles for inspection $42.00 reinspecton fee 2/22/2002 10:19:15 AM
|
Final | 2/22/2002 | 2/22/2002 | 2/22/2002 | P | FAIL |
Mike Kinnear
|
|
|
fn phil ###-#### 300.11(a) raceways & cable shall not be supprted by ceiling grid 2/22/2002 3:35:04 PM
|
Electrical Rough-In | 1/25/2002 | 1/25/2002 | 1/25/2002 | P | PART |
Jack Frank
|
|
|
r/i- nathan- ###-#### --call 1st before insp walls only no ceiling needs to support MC cables as NEC300.11 states on it's own identified support wires 1/25/2002 3:53:55 PM
|