Electrical Rough-In | 7/2/2002 | 7/2/2002 | 7/2/2002 | P | PASS |
Tim McCullough
|
|
|
r/i- rick- ###-####
ri/ok 7/2/2002 12:42:58 PM
|
Temporary Service | 2/7/2002 | 2/7/2002 | 2/7/2002 | P | PASS |
Jack Frank
|
|
|
###-#### RICK t/s u/g new ok 2/7/2002 3:41:14 PM
|
Temporary Service | 1/29/2002 | 1/30/2002 | 1/30/2002 | A | FAIL |
Marv Burrus
|
|
|
RICK CELL # ###-#### OFFICE # ###-#### MIKE , I REMEMBERD THE PHONE #'S THIS TIME !!! ///DLD. nec: 250-92 (a)(2), (b)(4). 1/30/2002 9:51:18 AM
|
Temporary Service | 1/28/2002 | 1/29/2002 | 1/29/2002 | A | FAIL |
Mike Kinnear
|
|
|