Final | 8/7/2002 | 8/9/2002 | 8/9/2002 | P | PASS |
Tim McCullough
|
|
|
JASON ###-#### PLEASE CALL 1ST FOR ACCESS
final/ok 8/9/2002 2:37:50 PM
|
Final | 8/5/2002 | 8/6/2002 | 8/6/2002 | A | NH |
Tim McCullough
|
|
|
Scheduled by a contractor via Hello! on 08/05/2002 at 15:26:23. Contact: ###-####.no acc left card 8/6/2002 4:27:21 PM
|
Final | 2/5/2002 | 2/5/2002 | 2/5/2002 | P | FAIL |
Jack Frank
|
|
|
###-#### cor. posted called 110.3(b)shall not type off of factory wire bus in p/s shall install manufactures listed fuse block in blank space for a/c branch circuit, 240.52 shall install type S fuses where evidence of overfusing, 210.63 shall provide gfci protected outside outlet for a/c 2/5/2002 5:45:39 PM
|