Information based on query as of Friday, July 19, 2024.
Permit Information
Permit NumberELE02-00608
StatusFinaled
Name A-1 ELECTRIC
Site Address 1650 N HILTON ST
Project NamePRECON TECHNOLOGIES
Customer Number 
ePlanReview 
Description
3/6/02/precon technologies/outletas, lights, ele wiring of building/initial cert of value $9,990/mls 5-15-03 NO ADDITIONAL VALUE ///DLD
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/31/20034/1/20034/1/2003APASS
DetailsJoe Ray
###-####
Final3/28/20033/28/20033/28/2003PFAIL
DetailsJack Frank
DAN; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 410.14 (B) needs access too box, covered by fixture, 110.12 (A) seal all unused openings 3/28/2003 2:03:23 PM
ELE-Aging Inspection2/27/20032/27/20032/27/2003 PART
DetailsJack Frank
wsuc 2/27/2003 7:42:12 AM
ELE-Aging Inspection12/16/200212/16/200212/16/2002 PART
DetailsJack Frank
W S U C 12/16/2002 2:03:54 PM
Final8/23/20028/23/20028/23/2002PCANC
DetailsJack Frank
###-#### dan no final see added p/s 8/23/2002 5:42:48 PM
Permanent Service8/23/20028/23/20028/23/2002PPASS
DetailsJack Frank
p/s u/g new ok
Permanent Service8/21/20028/21/20028/21/2002PFAIL
DetailsJack Frank
Phone #: ###-#### cor. posted called all corrections not made and needs to bond nipples with #2 as 250.66 states stills needs to install locknuts to meet intent of 300.10,and 12 8/22/2002 12:05:51 PM
Permanent Service8/6/20028/6/20028/6/2002PFAIL
DetailsJack Frank
cor. , and $45.00 reinspection fee due posted called left message 300.10, and 14 use locknuts inside and outside of cabinets and boxes where rigid conduit is used , bond bushings where R E washers are used, 250.8 no sheet metal screws for bonding ,and grounding, 344.46 bushing for rigid nipples, 250.24 connect grd and nuetrals at p/s 250.28(A) install bond screws 8/6/2002 5:48:41 PM
Electrical Rough-In3/20/20023/21/20023/21/2002APASS
DetailsJack Frank
###-#### DAN ok 3/21/2002 10:47:01 AM
Electrical Rough-In3/20/20023/20/20023/20/2002PFAIL
DetailsJack Frank
###-#### cor. posted called left message 300.4 protection for MC cable 11/4 3/20/2002 3:01:40 PM
Electrical Rough-In3/11/20023/11/20023/11/2002PNR
DetailsJack Frank
###-#### job not ready called 3/11/2002 4:56:50 PM