Final | 4/10/2002 | 4/11/2002 | 4/11/2002 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 04/10/2002 at 10:13:54. Contact: ###-####. ok 4/11/2002 11:08:00 AM
|
Final | 4/8/2002 | 4/9/2002 | 4/9/2002 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 04/08/2002 at 13:52:39. Contact: ###-####. cor. posted called 314.20 box in paneded wall shall be flush desk area, 314.29 shall not bury box jbox covered by the desk, 410.14 provide access to box , surface mounted flourescent fixture 4/9/2002 3:32:42 PM
|
Electrical Rough-In | 3/21/2002 | 3/22/2002 | 3/22/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### corrections not made called still needs to strap mc within 12 inches of boxes and provide 1 1/4 for MC and flex 3/22/2002 10:32:04 AM
|
Electrical Rough-In | 3/22/2002 | 3/22/2002 | 3/22/2002 | P | PASS |
Jack Frank
|
|
|
###-#### r/i ok corrections made 3/22/2002 3:40:08 PM
|
Electrical Rough-In | 3/21/2002 | 3/21/2002 | 3/21/2002 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 03/21/2002 at 08:06:37. Contact: ###-####. cor. posted called 300.4 nai plates and 1 1/4, 300.11(2)(B), 330.30(C) 314.29 4 sq box in hallway 3/21/2002 3:32:02 PM
|