Rough-In Permanent Service | 4/9/2002 | 4/10/2002 | 4/10/2002 | A | PASS |
Jim Schmer
|
|
|
Scheduled by Inspector: 324 On 4/9/2002 5:07:44 PM Conference p/s u/g new - ok 4/10/2002 10:12:31 AM
|
Final | 4/8/2002 | 4/9/2002 | 4/9/2002 | A | CANC |
Jack Frank
|
|
|
marv ###-#### access to address from Ash Park lane see added p/s inspection 4/9/2002 2:34:33 PM
|
Permanent Service | 4/9/2002 | 4/9/2002 | 4/9/2002 | P | PART |
Jack Frank
|
|
|
Added by Inspector: 315 On 4/9/2002 2:35:27 PM need to meet with contractor no p/s
|
Permanent Service | 4/9/2002 | 4/9/2002 | 4/9/2002 | P | FAIL |
Jack Frank
|
|
|
Scheduled by Inspector: 315 On 4/9/2002 2:35:55 PM cor. posted called UAC 305.1 u/g and grd grid covered before inspection, and installed without permit and by non licesed persons(BMC 4-05-08) 110.12 seal unused openings around pvc, 300.12 shall maintain mechanicl cotinunity of raceway ent to lfnc, and flnc to pvc, with listed and approved fittings, 312.5(A) for grd wire entering bottom of cabinets 4/9/2002 5:22:35 PM
|