Permanent Service | 4/17/2002 | 4/18/2002 | 4/18/2002 | A | PASS |
Pat Lass
|
|
|
perm ser lloyd ###-####
P/S O/H R Ok 4/18/2002 10:20:15 AM
|
Permanent Service | 4/16/2002 | 4/17/2002 | 4/17/2002 | A | FAIL |
Pat Lass
|
|
|
per ser lloyd ###-####
No guy kit phone wires supported from mast and 8 circuits with only 2 neutrals 4/17/2002 10:12:42 AM
|
Permanent Service | 4/15/2002 | 4/15/2002 | 4/15/2002 | P | FAIL |
Jack Frank
|
|
|
or 1hr before you go ###-#### cor. posted called left # 200.7 shall not use white wire for phase conductors 250.8 no SMS jbox, 250.52,or 104 if electrode within 5ft if not bond anyplace, 310.15 derate conductors over there in a raceway 4/15/2002 4:24:11 PM
|