Information based on query as of Tuesday, July 2, 2024.
Permit Information
Permit NumberELE02-01090
StatusFinaled
Name SZURGOT ELECTRIC
Site Address 5998 S QUAMASH WAY
Project NameWILLOW TREE DENTAL
Customer Number 
ePlanReview 
Description
ELECTRICAL WIRING WILLOW TREE DENTAL OFFICE PER INITIAL CERT OF VALUE $48,000.00//RE-OPENING STATUS & ADDING PARKING LOT LIGHTS PER LINDA H. THIS VALUE IS ALREADY INCLUDED FOR THE LIGHTS./MLS/7/1/02
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/10/20027/10/20027/10/2002PPASS
DetailsMike Kinnear
###-#### steve ok final site lighting note did not inspect under ground conduit 7/10/2002 1:21:47 PM
Electrical Rough-In7/1/20027/2/20027/2/2002AFAIL
DetailsMike Kinnear
STEVE ###-#### R/I correction NEC300-5 24inches depth under parking lot 7/2/2002 9:27:59 AM
Final6/25/20026/26/20026/26/2002APART
DetailsMike Kinnear
fn insp- ###-####- steve temp. occ. signed light bulbs in suffet rec. can not approved for outdoor use 6/26/2002 12:17:24 PM
Final6/26/20026/26/20026/26/2002PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 06/26/2002 at 10:30:54. Contact: ###-####. ok final 6/26/2002 2:43:36 PM
Electrical Rough-In6/25/20026/25/20026/25/2002PPART
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 06/25/2002 at 10:09:53. Contact: ###-####.ok cover ceiling except around for tv outlets 6/25/2002 1:35:14 PM
Final6/25/20026/25/20026/25/2002PCANC
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 06/25/2002 at 10:06:17. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 06/25/2002 at 10:08:50.
Permanent Service6/21/20026/24/20026/24/2002APASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 06/21/2002 at 13:27:34. Contact: ###-####. p/s u/g n ok 6/24/2002 9:23:50 AM
Permanent Service6/20/20026/21/20026/21/2002ANR
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 06/20/2002 at 14:05:22. Contact: ###-####. not ready no wire to ct can 6/21/2002 9:35:31 AM
Permanent Service5/6/20025/6/20025/6/2002PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 05/06/2002 at 11:26:42. Contact: ###-####. p/s u/g n ok note insulation on feeder wires damaged- had contractor meg test system ok test -wired in pvc conduit 5/6/2002 1:26:49 PM
Electrical Rough-In5/2/20025/3/20025/3/2002APASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 05/02/2002 at 16:26:45. Contact: ###-####. no p/s more violations 250.8
r/i ok only $42.00 reinspection fee due
5/3/2002 11:22:35 AM
Permanent Service5/3/20025/3/20025/3/2002PFAIL
DetailsJim Schmer
Scheduled by a contractor via Hello! on 05/03/2002 at 10:09:17. Contact: ###-####. told to repull conductors or meg out conductors to sub-panels, and entire length of conductor has to bee in lugs. 5/3/2002 2:37:36 PM
Rough-In Permanent Service5/3/20025/3/20025/3/2002APART
DetailsMike Kinnear
per Mike K. ok cover ri fail service NEC250.8 reinspection fee $45.00 315 & 412 did inspection 5/3/2002 9:52:29 AM
Rough-In Permanent Service5/1/20025/2/20025/2/2002AFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 05/01/2002 at 13:58:52. Contact: ###-####. partial correction posted only job not complete yet called 300.10 fittings not tight,110.14, 300.4, 300.3(B), 250.148 5/2/2002 1:57:48 PM
Rough-In Permanent Service5/2/20025/2/20025/2/2002AFAIL
DetailsMike Kinnear
PER MIKE KINNEAR did inspection with 315 NEC300.10,250.148,110.14,300.3(B),330.30(C),314.16, & survey 314.20 5/2/2002 3:49:55 PM
Rough-In Permanent Service5/2/20025/2/20025/2/2002AFAIL
DetailsJack Frank
PER MIKE KINNEAR cor. posted called 300.10 fittings at boxes 250.148,300.3(B) feeders to sub panels, 300.4 plates and 1 1/4
330.30(C), 314.16 box fill, surveyed 314.20 needs 3/4 inch raised rings for 5/8 rock 5/2/2002 5:49:07 PM
Electrical Rough-In5/1/20025/1/20025/1/2002APART
DetailsMike Kinnear
CONFERENCE WITH CONTRACTOR ok 5/1/2002 2:18:53 PM
Rough-In Permanent Service4/30/20025/1/20025/1/2002AFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 04/30/2002 at 09:29:54. Contact: ###-####. needs to strap MC within 12 inches of soffit lights 5/1/2002 1:52:32 PM