Final | 7/10/2002 | 7/10/2002 | 7/10/2002 | P | PASS |
Mike Kinnear
|
|
|
###-#### steve ok final site lighting note did not inspect under ground conduit 7/10/2002 1:21:47 PM
|
Electrical Rough-In | 7/1/2002 | 7/2/2002 | 7/2/2002 | A | FAIL |
Mike Kinnear
|
|
|
STEVE ###-#### R/I correction NEC300-5 24inches depth under parking lot 7/2/2002 9:27:59 AM
|
Final | 6/25/2002 | 6/26/2002 | 6/26/2002 | A | PART |
Mike Kinnear
|
|
|
fn insp- ###-####- steve temp. occ. signed light bulbs in suffet rec. can not approved for outdoor use 6/26/2002 12:17:24 PM
|
Final | 6/26/2002 | 6/26/2002 | 6/26/2002 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/26/2002 at 10:30:54. Contact: ###-####. ok final 6/26/2002 2:43:36 PM
|
Electrical Rough-In | 6/25/2002 | 6/25/2002 | 6/25/2002 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/25/2002 at 10:09:53. Contact: ###-####.ok cover ceiling except around for tv outlets 6/25/2002 1:35:14 PM
|
Final | 6/25/2002 | 6/25/2002 | 6/25/2002 | P | CANC |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/25/2002 at 10:06:17. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 06/25/2002 at 10:08:50.
|
Permanent Service | 6/21/2002 | 6/24/2002 | 6/24/2002 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/21/2002 at 13:27:34. Contact: ###-####. p/s u/g n ok 6/24/2002 9:23:50 AM
|
Permanent Service | 6/20/2002 | 6/21/2002 | 6/21/2002 | A | NR |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 06/20/2002 at 14:05:22. Contact: ###-####. not ready no wire to ct can 6/21/2002 9:35:31 AM
|
Permanent Service | 5/6/2002 | 5/6/2002 | 5/6/2002 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 05/06/2002 at 11:26:42. Contact: ###-####. p/s u/g n ok note insulation on feeder wires damaged- had contractor meg test system ok test -wired in pvc conduit 5/6/2002 1:26:49 PM
|
Electrical Rough-In | 5/2/2002 | 5/3/2002 | 5/3/2002 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 05/02/2002 at 16:26:45. Contact: ###-####. no p/s more violations 250.8
r/i ok only $42.00 reinspection fee due
5/3/2002 11:22:35 AM
|
Permanent Service | 5/3/2002 | 5/3/2002 | 5/3/2002 | P | FAIL |
Jim Schmer
|
|
|
Scheduled by a contractor via Hello! on 05/03/2002 at 10:09:17. Contact: ###-####. told to repull conductors or meg out conductors to sub-panels, and entire length of conductor has to bee in lugs. 5/3/2002 2:37:36 PM
|
Rough-In Permanent Service | 5/3/2002 | 5/3/2002 | 5/3/2002 | A | PART |
Mike Kinnear
|
|
|
per Mike K. ok cover ri fail service NEC250.8 reinspection fee $45.00 315 & 412 did inspection 5/3/2002 9:52:29 AM
|
Rough-In Permanent Service | 5/1/2002 | 5/2/2002 | 5/2/2002 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 05/01/2002 at 13:58:52. Contact: ###-####. partial correction posted only job not complete yet called 300.10 fittings not tight,110.14, 300.4, 300.3(B), 250.148 5/2/2002 1:57:48 PM
|
Rough-In Permanent Service | 5/2/2002 | 5/2/2002 | 5/2/2002 | A | FAIL |
Mike Kinnear
|
|
|
PER MIKE KINNEAR did inspection with 315 NEC300.10,250.148,110.14,300.3(B),330.30(C),314.16, & survey 314.20 5/2/2002 3:49:55 PM
|
Rough-In Permanent Service | 5/2/2002 | 5/2/2002 | 5/2/2002 | A | FAIL |
Jack Frank
|
|
|
PER MIKE KINNEAR cor. posted called 300.10 fittings at boxes 250.148,300.3(B) feeders to sub panels, 300.4 plates and 1 1/4
330.30(C), 314.16 box fill, surveyed 314.20 needs 3/4 inch raised rings for 5/8 rock 5/2/2002 5:49:07 PM
|
Electrical Rough-In | 5/1/2002 | 5/1/2002 | 5/1/2002 | A | PART |
Mike Kinnear
|
|
|
CONFERENCE WITH CONTRACTOR ok 5/1/2002 2:18:53 PM
|
Rough-In Permanent Service | 4/30/2002 | 5/1/2002 | 5/1/2002 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 04/30/2002 at 09:29:54. Contact: ###-####. needs to strap MC within 12 inches of soffit lights 5/1/2002 1:52:32 PM
|