DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/28/20025/29/20025/29/2002APASS
DetailsTim McCullough
final ok 5/29/2002 3:15:40 PM
Final5/28/20025/28/20025/28/2002PNH
DetailsTim McCullough
Scheduled by a contractor via Hello! on 05/28/2002 at 07:11:12. Contact: ###-####.
no access
befor 3:oo
5/28/2002 5:44:18 PM
Electrical Rough-In5/13/20025/14/20025/14/2002APASS
DetailsJack Frank
warren ###-#### r/i ok 5/14/2002 10:10:46 AM
Electrical Rough-In5/7/20025/8/20025/8/2002APART
DetailsJack Frank
WARREN ###-#### walls ok 5/8/2002 10:43:29 AM
Electrical Rough-In5/6/20025/7/20025/7/2002ANR
DetailsJack Frank
r/i- insp on walls- warren- ###-####
Electrical Rough-In5/6/20025/6/20025/6/2002PFAIL
DetailsJack Frank
INTERIOR WALL INSPECT ###-#### WARREN cor. posted called 110.14(A) stranded wire under grd screws not allowed, 314.20 mud rings shall be flush with combustible material 5/6/2002 4:59:08 PM
Electrical Rough-In4/25/20024/25/20024/25/2002AFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 04/25/2002 at 07:10:01. Contact: ###-####. u/g covered before inspection called contractor will uncover trench, and call for reinspection 4/25/2002 11:11:51 AM
Electrical Rough-In4/25/20024/25/20024/25/2002PPART
DetailsJack Frank
TRENCH ###-#### u/g ok (feeder to portable class rm back of school, need 16 inch j box in attic for straight thru pull box 314.28 4/25/2002 3:33:24 PM