Final | 8/13/2002 | 8/13/2002 | 8/13/2002 | P | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 08/13/2002 at 08:28:10. Contact: ###-####.
|
Electrical Rough-In | 6/10/2002 | 6/11/2002 | 6/11/2002 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 06/10/2002 at 16:23:13. Contact: ###-####. ok 6/11/2002 12:26:42 PM
|
Permanent Service | 6/10/2002 | 6/10/2002 | 6/10/2002 | P | PASS |
Jack Frank
|
|
|
p/s u/g new ok
|
Rough-In Permanent Service | 6/10/2002 | 6/10/2002 | 6/10/2002 | P | FAIL |
Jack Frank
|
|
|
john ###-####--r/i & ser cor. posted called 210.52 (A&B) needs outlets on 20 kit circuit foo feed outlets, in dinning rm and breakfast nook, 314.20 outside boxes not flush 210.52(F) & 210.11(C) all outlets in laundry area, shall be 20 amp laundry circuit, 300.4 11/4 inches needed see added p/s inspection for info 6/10/2002 3:10:35 PM
|