Final | 12/18/2002 | 12/18/2002 | 12/18/2002 | P | PASS |
Jack Frank
|
|
|
School is out at 2:50. Please schedule accordingly. Call me to meet you there. Thanks, Heath; Phone #: ###-#### Internet Inspection Request from: Joe Thomasok corrections made 12/18/2002 5:33:49 PM
|
Final | 8/21/2002 | 8/22/2002 | 8/22/2002 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 08/21/2002 at 11:27:58. Contact: ###-####. conference ok noted on correction does listed fan coil unit need to meet N E C requirerments 300.10, 344.28 and 46 8/22/2002 6:01:40 PM
|
Electrical Rough-In | 8/16/2002 | 8/16/2002 | 8/16/2002 | A | FAIL |
Jack Frank
|
|
|
cor. posted met with contractor and PLass 110.3(B) max 15 amp feed too fan coil unit, 386.22 wire fill shall not exceed what raceway is designed for, 300.16 shall provide a terminal fitting for abrasion where cable exits raceway
|
Final | 8/15/2002 | 8/16/2002 | 8/16/2002 | A | FAIL |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 08/15/2002 at 16:38:33. Contact: ###-####.
110.3 and abrasion protection. 8/16/2002 10:08:33 AM
|