Final | 8/14/2002 | 8/14/2002 | 8/14/2002 | P | PASS |
Joe Ray
|
|
|
###-####
|
Final | 8/6/2002 | 8/6/2002 | 8/6/2002 | P | FAIL |
Jack Frank
|
|
|
###-#### DAVID not ready called needs shelves in clothes closet so I can check for clearence, and mount outside WP cover for horizontal plane everything else checked out OK
8/6/2002 6:52:20 PM
|
Electrical Rough-In | 7/15/2002 | 7/16/2002 | 7/16/2002 | A | PASS |
Jack Frank
|
|
|
r/i david- ###-#### ok 7/16/2002 11:56:54 AM
|
Electrical Rough-In | 7/12/2002 | 7/15/2002 | 7/15/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### cor. posted called 300.4 (A)(1)&(D) 210.52 (A) needs 2 outlets for wall space dinning rm 11.14(B) grd splices loose, 314.16 box fill no violation to be retained 2 box in kit. 7/15/2002 1:08:55 PM
|
Rough-In Permanent Service | 6/27/2002 | 6/28/2002 | 6/28/2002 | A | PASS |
Jack Frank
|
|
|
###-#### no r/i
p/s o/h rec ok 6/27/2002 5:54:54 PM
|
Rough-In Permanent Service | 6/26/2002 | 6/27/2002 | 6/27/2002 | P | FAIL |
Jack Frank
|
|
|
###-#### cor. posted met with contractor250.66 needs #4 GEC 250.52(A)(1) terminate GEC within 5 ft of where u/g enters,250.53(D)(2) needs 2 grd rods ,230.24(A) needs 8 ft over roof 6/27/2002 3:48:16 PM
|