Final | 10/17/2002 | 10/17/2002 | 10/17/2002 | P | PASS |
Pat Lass
|
|
|
###-#### HERSZHEL PLEASE CALL FOR ACCESS
|
Electrical Rough-In | 6/28/2002 | 7/1/2002 | 7/1/2002 | A | FAIL |
Jack Frank
|
|
|
HERSCHEL ###-#### PLEASE CALL SO HE CAN LET YOU ON cor. posted called 110.3(B) needs #6 as manufacture states use manufactrues listed breaker 358.22 i/2 conduit not large enough for conductors, 358.12 emt not approved where subject to damage on ground 7/1/2002 1:47:22 PM
|