Final | 7/30/2002 | 8/1/2002 | 8/1/2002 | A | FAIL |
Jim Schmer
|
|
|
###-#### water pipes still below panel - failed. 8/1/2002 9:23:08 AM
|
Final | 8/1/2002 | 8/1/2002 | 8/1/2002 | P | PASS |
Jim Schmer
|
|
|
|
Final | 7/30/2002 | 7/31/2002 | 7/31/2002 | A | PART |
Pat Lass
|
|
|
###-####
Signed T/O 7/31/2002 8:43:29 AM
|
Final | 7/29/2002 | 7/30/2002 | 7/30/2002 | A | FAIL |
Pat Lass
|
|
|
###-#### john
250.148 and boxes flush 7/30/2002 11:37:43 AM
|
Final | 7/30/2002 | 7/30/2002 | 7/30/2002 | P | FAIL |
Jack Frank
|
|
|
john ; Phone #: ###-#### cor. posted 110.26(F)(1) move panels , or remove water piping from below panel for required clearence, 250.104 shall bond hot and cold water piping 7/30/2002 5:32:31 PM
|
Final | 7/25/2002 | 7/29/2002 | 7/29/2002 | A | FAIL |
Pat Lass
|
|
|
###-#### JOHN
derate conductors in 2" conduit 7/29/2002 11:11:58 AM
|
Final | 7/29/2002 | 7/29/2002 | 7/29/2002 | P | NR |
Pat Lass
|
|
|
###-#### JOHN
|
Rough-In Permanent Service | 7/1/2002 | 7/2/2002 | 7/2/2002 | A | PASS |
Jim Schmer
|
|
|
###-#### JOHN basement ok 7/2/2002 9:09:31 AM
|
Electrical Rough-In | 7/1/2002 | 7/1/2002 | 7/1/2002 | P | PASS |
Jim Schmer
|
|
|
r/i john ###-#### main floor 7/1/2002 1:16:10 PM
|