Final | 8/21/2002 | 8/21/2002 | 8/21/2002 | P | PASS |
Joe Ray
|
|
|
Phone #: ###-####
|
Electrical Rough-In | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### correction not made needs to replace single gang box in dinning by stairs broken out K O called 7/9/2002 12:30:30 PM
|
Rough-In Permanent Service | 7/9/2002 | 7/9/2002 | 7/9/2002 | P | PASS |
Jack Frank
|
|
|
john ###-#### r/i & ser ok
p/s u/g new ok 7/9/2002 6:31:21 PM
|
Electrical Rough-In | 7/8/2002 | 7/8/2002 | 7/8/2002 | P | FAIL |
Jack Frank
|
|
|
ALAN ###-#### cor. not made called 7/8/2002 5:06:23 PM
|
Electrical Rough-In | 7/3/2002 | 7/5/2002 | 7/5/2002 | A | FAIL |
Jack Frank
|
|
|
ALAN ###-#### corrections not made and more created shall not feed outlet in living rm from kit. circuit called left message 7/5/2002 11:40:15 AM
|
Rough-In Permanent Service | 7/2/2002 | 7/3/2002 | 7/3/2002 | P | FAIL |
Jack Frank
|
|
|
ALAN ###-#### 110.14 ringed wire meter, 314.20 boxes shall be set out 1/2 inch, 300.4 11/4 inch on studs, 210.52(A) needs outlet wall space in upstairs bed rm and living rm by stairs cor. posted called 7/3/2002 1:01:45 PM
|