Final | 9/26/2002 | 9/27/2002 | 9/27/2002 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok 9/27/2002 12:20:45 PM
|
Electrical Rough-In | 9/26/2002 | 9/26/2002 | 9/26/2002 | P | PART |
Jack Frank
|
|
|
cover for u/g post light ok 9/26/2002 4:50:33 PM
|
Final | 9/24/2002 | 9/25/2002 | 9/25/2002 | A | FAIL |
Jack Frank
|
|
|
ron-key by ser in cable tv box-side door will open gar side door; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor.and $45.00 fee due posted called outlet in master bed rm closet off of bath shall be on bath circuit with gfci protection no door at closet entry 200.11 kit,dinning rm shall uncover u/g to yard light no inspection was done,or called for 9/25/2002 1:18:27 PM
|
Electrical Rough-In | 7/31/2002 | 7/31/2002 | 7/31/2002 | P | PASS |
Jack Frank
|
|
|
###-#### ron cor. made r/i ok
p/s u/g new ok 7/31/2002 5:59:18 PM
|
Rough-In Permanent Service | 7/29/2002 | 7/30/2002 | 7/30/2002 | A | FAIL |
Jack Frank
|
|
|
; Phone #: ###-#### cor. posted called 300.4, 300.14, 210.52(A), 314.20, 250.148, 314.43, 334.24 kinks, and bends in cables less than 5 times diameter of cable. low voltage coe. posted for homeowner needs connector at all j boxes for ENT, cables need clamps at all boxes and cabinets, 314.20 , 314.43 7/30/2002 1:11:39 PM
|