Final | 7/25/2002 | 7/26/2002 | 7/26/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### ben cor. posted 240.24(D) sub panel not allowed in closet under stairs, 300.10 loose locknuts, and fittings bond bushings for r e washers, 110.3(B) use listed fittings for flex, and no plumbing fittings to be used 310.16 shall provide proper overcurrent protection for #12 and #14 awg , 240.21 (2) shall terminate tap from panel bus to sub panel in breaker,or fuses, 250.24(A)(5) isolate grds and nuetrals at sub panel and pump disconnect 200.7 shall ID white wire used as phase conductor, 344.46 bushings for rigid nipples. 348.30 secure flex 7/26/2002 12:40:25 PM
|