Final | 2/4/2003 | 2/4/2003 | 2/4/2003 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/4/2003 at 8:30:48 AM. Contact: ###-####. ok 2/4/2003 12:31:44 PM
|
Rough-In Permanent Service | 8/7/2002 | 8/7/2002 | 8/7/2002 | P | PASS |
Tim McCullough
|
|
|
Scheduled by a contractor via Hello! on 08/07/2002 at 08:36:50. Contact: ###-####.
ri/ok
ps/ug/new/ok 8/7/2002 3:38:21 PM
|
Rough-In Permanent Service | 8/2/2002 | 8/6/2002 | 8/6/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### cor. posted called 300.4(D) 11/4 inches,300.14 6 inches free length 210.52(B) formal dinning rm shall be on small appliance branch circuit, 210.52 (D) outlet within 3ft of both sinks M bath, 110.14 (B) all splices shall be made up tight grd wires, 110.12(A) seal, or replace plastic boxes with unused K Os, 11.3(B) replace 2,3,4 gang boxes with broken internal clamps, move jbox for j tub so it is accessible 8/6/2002 3:10:24 PM
|