Final | 8/29/2002 | 8/29/2002 | 8/29/2002 | P | PASS |
Jim Schmer
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
Permanent Service | 8/22/2002 | 8/22/2002 | 8/22/2002 | P | CANC |
Jack Frank
|
|
|
###-#### see added t/s 8/22/2002 4:10:04 PM
|
Temporary Service | 8/22/2002 | 8/22/2002 | 8/22/2002 | P | PASS |
Jack Frank
|
|
|
t/s o/h rec. fire job
|
Permanent Service | 8/21/2002 | 8/21/2002 | 8/21/2002 | P | FAIL |
Jack Frank
|
|
|
SHAWN ; Phone #: ###-#### cor. posted called 250.104 asure wter pipe is bonded bond hot and cold at both wter heaters, 250.8 no SMS for bond or grd p/s disconnect, 110.3(B) sue manufactures breakers only sub panel, 200.6and 7 blk wires used as neutrals white,as phase 310.16 is feeder to sub panel #6,or#4 protect at proper amps called 8/21/2002 6:20:06 PM
|
Permanent Service | 8/20/2002 | 8/20/2002 | 8/20/2002 | P | FAIL |
Jack Frank
|
|
|
###-#### cor. posted called 250.28 bond screw,250.52,or104 grd or bond water system, 250.90 bond nipple between meter and p/s disconnect, 250 53(D)(2) 2 grd rods 230.28 strap mast, 110.26 make sure panel has clearence and dedicated space 8/20/2002 3:48:19 PM
|