Information based on query as of Monday, July 1, 2024.
Permit Information
Permit NumberELE02-02685
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 1055 N CURTIS RD
Project NameST ALS-S TOWER
Customer Number1602
ePlanReview 
Description
8/28/02/st al's/5th floor remodel Phase "1"/ fire system, security system, nurses intercom, lighting, wiring, panel boxes/initial cert of value $599,838/mls 1-28-04 FINAL TOTAL $ 648,892.00
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/19/20032/20/20032/20/2003APASS
DetailsJack Frank
ok phase 1 west 2/20/2003 9:44:52 AM
Final2/19/20032/19/20032/19/2003PCANC
DetailsJack Frank
called will do it 02-20-03 AM
2/19/2003 4:57:36 PM
Final2/13/20032/13/20032/13/2003PPART
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung perm occupancy ok for west half phase one no final till all cor. for clear space above gear completed 2/13/2003 12:29:42 PM
Electrical Rough-In2/6/20032/6/20032/6/2003PPASS
DetailsTim McCullough
ceiling insp -ernest; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ceilings-526,27,28 ok 2/6/2003 1:39:43 PM
Electrical Rough-In1/29/20031/30/20031/30/2003APART
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ceilings west phase ok 1/30/2003 9:22:09 AM
Electrical Rough-In1/8/20031/8/20031/8/2003PPART
DetailsJack Frank
###-#### ERNST r/i rms 526, 527 1/8/2003 5:25:20 PM
Electrical Rough-In12/27/200212/27/200212/27/2002PPART
DetailsJack Frank
###-#### ernest (voice pager) r/i rms 528,529 12/27/2002 4:21:51 PM
Electrical Rough-In12/4/200212/4/200212/4/2002APART
DetailsJack Frank
conference with Jim S , Quality, concerning clearence for gear 2nd floor 12/4/2002 11:41:01 AM
Electrical Rough-In11/27/200212/2/200212/2/2002APART
DetailsJoe Ray
ERNEST CONTACT # IS FOR VOICE PAGER INSPECTION FOR EAST CORE AREA, AND GROUNDING IN THE ELE ROOMS; Phone #: ###-#### Internet Inspection Request from: Darla Downs grd ok /conduits need supports 12/2/2002 11:47:05 AM
Electrical Rough-In12/2/200212/2/200212/2/2002PPASS
DetailsTim McCullough
###-#### ernest
ok to cover walls 12/2/2002 2:03:37 PM
Electrical Rough-In11/26/200211/26/200211/26/2002PPART
DetailsJack Frank
conference ok correction posted 110.26(E),(F)(1) for electrical gear added oon 2 nd floor
Electrical Rough-In11/22/200211/22/200211/22/2002PPART
DetailsJack Frank
conference for clearence new gear 2nd floor
Final11/22/200211/22/200211/22/2002PCANC
DetailsJack Frank
2nd floor only ###-#### see added r/i 11/22/2002 6:19:09 PM
Electrical Rough-In11/18/200211/19/200211/19/2002APART
DetailsJack Frank
conference on east end electrical room ###-#### ok 11/19/2002 12:00:18 PM
Electrical Rough-In11/4/200211/5/200211/5/2002PPASS
DetailsTim McCullough
5th floor ###-#### pager ernest
ok to cover s.w. pat. rms 11/5/2002 2:43:59 PM
Electrical Rough-In10/18/200210/21/200210/21/2002APART
DetailsJack Frank
ernie ###-#### part walls for 6 rooms 10/21/2002 11:53:02 AM
Electrical Rough-In10/21/200210/21/200210/21/2002PPART
DetailsJack Frank
ernest ; Phone #: ###-#### Internet Inspection Request from: Annette Moore met with contractor in the AM 10/21/2002 3:36:09 PM
Electrical Rough-In10/18/200210/18/200210/18/2002PCANC
DetailsJack Frank
###-#### ernest ran out of time will do 10/21/02 AM 10/18/2002 6:45:30 PM
Electrical Rough-In10/15/200210/15/200210/15/2002PPART
DetailsJack Frank
###-#### walls in rooms except bed locations
10/15/2002 2:43:42 PM
Electrical Rough-In10/10/200210/10/200210/10/2002PPART
DetailsJack Frank
ROOM 535 PAGER ###-#### ERNEST conference only pointed out violation in rm 535 , and new panels that do not meet 110.26 clearence 10/10/2002 6:13:48 PM
Electrical Rough-In10/8/200210/8/200210/8/2002PPART
DetailsJack Frank
conference with Ernie of Quality grd for xformers 5th floor
Electrical Rough-In9/30/200210/1/200210/1/2002APART
DetailsJack Frank
just core area middle section 5th floor walls 10/1/2002 2:41:34 PM
Electrical Rough-In9/30/20029/30/20029/30/2002PFAIL
DetailsJack Frank
ernist ( this is a voice pager # )please page him so he can show you what needs to be inspected; Phone #: ###-#### Internet Inspection Request from: Darla Downs called twice the number is not in service, could not make contact 9/30/2002 6:02:39 PM