Final | 1/26/2003 | 1/27/2003 | 1/27/2003 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 01/26/2003 at 19:46:52. Contact: ###-####. ok final 1/27/2003 9:44:19 AM
|
Final | 1/21/2003 | 1/22/2003 | 1/22/2003 | A | FAIL |
Jack Frank
|
|
|
FN DAVID- ###-#### cor. posted call 210.52 (C) (5) exception needs outlet too serve left side of sink (island) note both new, and existing outlets shall not extend more than 6 inches back from countertop edge 1/22/2003 9:14:23 AM
|
Electrical Rough-In | 9/11/2002 | 9/11/2002 | 9/11/2002 | P | PASS |
Mike Kinnear
|
|
|
CONFERENCE ###-#### ok cover ri 9/11/2002 2:01:41 PM
|
Rough-In Permanent Service | 9/10/2002 | 9/11/2002 | 9/11/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### need to meet with electrical contractor at job site called left message kitchen area DW with 2 disposals on needs to replace plastic boxes with unused KOs outlet spacing and kitchen circuits ? 9/11/2002 12:07:11 PM
|