Final | 5/7/2008 | 5/8/2008 | 5/8/2008 | P | PASS |
Jack Frank
|
|
|
Customer thought this permit was final. Wants an inspector to go out. Armin ###-#### ok no power to 1 recept owner will correct
|
Final | 6/5/2003 | 6/6/2003 | 6/6/2003 | A | NR |
Jack Frank
|
|
|
###-#### need to talk with owner baseboard below outlets and no access furniture in the way 6/6/2003 9:42:13 AM
|
Electrical Rough-In | 10/21/2002 | 10/22/2002 | 10/22/2002 | A | PASS |
Tim McCullough
|
|
|
edin; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ri/ok 10/22/2002 12:19:30 PM
|
Electrical Rough-In | 10/2/2002 | 10/2/2002 | 10/2/2002 | P | FAIL |
Jack Frank
|
|
|
###-#### cor. posted met with owner UAC 301.1,and 305.1 shall uncover all u/g installed without permit,and required inspections 250.52(A)(3) shall install concrete encased elctrode and call for inspectins before cover, 33.30and 314.17(C) staple romex within 8 or 12 inches of boxes, 110.3(B) shall use only listed PVC electrical fittings, BCC shall have all makeup done before inspection requested 10/2/2002 4:35:11 PM
|