Final | 4/9/2003 | 4/9/2003 | 4/9/2003 | P | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
Electrical Rough-In | 11/12/2002 | 11/12/2002 | 11/12/2002 | P | PASS |
Pat Lass
|
|
|
cory- ###-####
P/S O/H R Ok 11/12/2002 2:29:53 PM
|
Electrical Rough-In | 11/6/2002 | 11/6/2002 | 11/6/2002 | P | FAIL |
Pat Lass
|
|
|
cory- ###-####
300.4 Protection Against Physical Damage.
Where subject to physical damage, conductors shall be adequately protected.
(D) Cables and Raceways Parallel to Framing Members.
314.17 Conductors Entering Boxes, Conduit Bodies, or Fittings.
Conductors entering boxes, conduit bodies, or fittings shall be protected from abrasion and shall comply with 314.17(A) through (D).
(B) Metal Boxes and Conduit Bodies.
…… Where raceway or cable is installed with metal boxes or conduit bodies, the raceway or cable shall be secured to such boxes and conduit bodies.
11/6/2002 1:00:36 PM
|