Final | 11/15/2002 | 11/18/2002 | 11/18/2002 | P | PASS |
Jack Frank
|
|
|
KEITH; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
p/s o/h rec. ok 11/18/2002 2:45:30 PM
|
Final | 11/14/2002 | 11/15/2002 | 11/15/2002 | A | CANC |
Jack Frank
|
|
|
###-#### GARY called could not hear message called orther number no contact, cor posted 250.53 (B) grd rod not 6ft apart,250.92 (A)(3) bond both ends of nipple between meter and p/s when GEC passes through it. 312.3 service panel shall be flush with finish surface and cover fit tight to panel,250.52 or 104 grd within 5 ft or bond 11/15/2002 2:26:30 PM
|
Permanent Service | 11/15/2002 | 11/15/2002 | 11/15/2002 | A | FAIL |
Jack Frank
|
|
|
see final inspection request for correction info
|
Final | 11/7/2002 | 11/8/2002 | 11/8/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### shall bring p/s change up too meet clearence and grounding called 11/8/2002 2:27:09 PM
|
Final | 11/6/2002 | 11/7/2002 | 11/7/2002 | A | PART |
Joe Ray
|
|
|
###-#### out side mast needs to be up to code no service at this time /reinspection required11/7/2002 11:31:49 AM 11/7/2002 11:33:16 AM
|