Permit Information
Permit NumberELE02-03586
StatusFinaled
Name B & J ELECTRIC INC
Site Address 2014 S BROXON ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/14/20031/14/20031/14/2003PPASS
DetailsJack Frank
Key is under 2x6 on deck railing. ; Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok cor. made 1/14/2003 6:27:15 PM
Final1/10/20031/13/20031/13/2003AFAIL
DetailsJack Frank
Key is located at back door on deck railing under 2x6 board. ; Phone #: ###-#### Internet Inspection Request from: Joe Thomas cor. fee due posted called 210.52(A) outlet required room off of laundry rm by access under stairs, line and load outlet counter by refer, needs gfci grd outlet on ungrd circuit hallway 1/13/2003 11:22:48 AM
Electrical Rough-In12/12/200212/12/200212/12/2002PPASS
DetailsJack Frank
CALL HEATH FIRST ###-#### ok 12/12/2002 4:28:58 PM
Electrical Rough-In12/11/200212/11/200212/11/2002PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 12/11/2002 at 10:32:14. Contact: ###-####. cor. posted 300.14, 250.66 bond water with #4 200.7 old wiring white shall not be used as phase wire, 210.70 light fixture shall light back area, 314.23 cutin boxes shall be rigidly mounted in finish surfaces, 314.20 boxes set back more than 1/4 inch check out all old wiring 12/11/2002 5:56:44 PM
Electrical Rough-In12/9/200212/9/200212/9/2002PFAIL
DetailsJack Frank
###-#### heath upstairs inspect on receptacle replacements nr needs plans at job site 12/9/2002 3:58:16 PM
Permanent Service11/21/200211/21/200211/21/2002PPASS
DetailsJack Frank
concrete is poured for ufer ground. Also, need O.K. for permanent service on exterior of house.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas
p/s u/g new ok 11/21/2002 3:49:16 PM
Electrical Rough-In11/19/200211/19/200211/19/2002PPART
DetailsJack Frank
r/i for concrete cover of elecrode only
Final11/19/200211/19/200211/19/2002PCANC
DetailsJack Frank
Ufer ground inspection. Contractor is moving window wells up and will add backfill to achieve proper cover.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas see added r/i 11/19/2002 5:29:18 PM
Permanent Service11/18/200211/19/200211/19/2002ANR
DetailsJack Frank
Ufer ground inspection on North side of the home in the back of the lot.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas called 11/19/2002 10:42:41 AM