Final | 8/3/2004 | 8/4/2004 | 8/4/2004 | A | PASS |
Pat Lass
|
|
|
Rex; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
Final | 7/30/2004 | 8/2/2004 | 8/2/2004 | P | PART |
William E Thomas
|
|
|
rex; Phone #: ###-#### Internet Inspection Request from: Cathy Chilesleft open on the inside is 410.8 closet fixture lamps not enclosed, 210.11B3 bathroom circuit dedicated for bathroom only (receps) 8/2/2004 3:56:25 PM
|
Conference | 5/17/2004 | 5/18/2004 | 5/18/2004 | P | PASS |
Joe Ray
|
|
|
Scheduled by a contractor via Hello! on 5/17/2004 at 6:07:20 PM. Contact: ###-####. plug in for electric curtains ok 5/18/2004 2:31:32 PM
|
Electrical Rough-In | 4/23/2004 | 4/23/2004 | 4/23/2004 | P | PART |
Pat Lass
|
|
|
###-####. Scheduled by a contractor via Hello! on 4/23/2004 at 8:45:56 AM. Contact: ###-####. 4/23/2004 11:39:08 AM
u/G In Back ok 4/23/2004 3:32:13 PM
|
Conference | 3/9/2004 | 3/10/2004 | 3/10/2004 | A | PART |
Pat Lass
|
|
|
REX; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
Conference | 3/2/2004 | 3/2/2004 | 3/2/2004 | P | DONE |
Pat Lass
|
|
|
rex; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
had conf 3/2/2004 2:26:28 PM
|
ELE-Request for Extension | 12/15/2003 | 12/15/2003 | 12/15/2003 | P | DONE |
Pat Lass
|
|
|
Project is still ongoing. ###-#### Rex
extend ok 12/15/2003 8:35:53 AM
|
Electrical Rough-In | 6/9/2003 | 6/10/2003 | 6/10/2003 | P | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 6/9/2003 at 5:28:58 PM. Contact: ###-####.
|
Electrical Rough-In | 6/6/2003 | 6/6/2003 | 6/6/2003 | P | PART |
Pat Lass
|
|
|
rex; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
had walk through conf 6/6/2003 3:40:17 PM
|
Electrical Rough-In | 5/28/2003 | 5/29/2003 | 5/29/2003 | A | PART |
Mike Kinnear
|
|
|
rex; Phone #: ###-#### Internet Inspection Request from: Annette Moore second floor south scheer wall only 5/29/2003 12:34:37 PM
|
Electrical Rough-In | 5/27/2003 | 5/27/2003 | 5/27/2003 | P | FAIL |
Jack Frank
|
|
|
REX; Phone #: ###-#### Internet Inspection Request from: Darla Downs r/i for garage only correction posted called left message 314.16 box fill and broken clamps 2 gang box by house to garage door 320.23 (A) protect cables by attic access in garage 5/27/2003 3:32:51 PM
|
Electrical Rough-In | 5/22/2003 | 5/22/2003 | 5/22/2003 | P | PART |
Mike Kinnear
|
|
|
rex garage only ; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok cover garage only 5/22/2003 9:44:24 PM
|
Electrical Rough-In | 5/22/2003 | 5/22/2003 | 5/22/2003 | P | PART |
Mike Kinnear
|
|
|
rex garage only ; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok cover garage only 5/22/2003 9:44:24 PM
|
Conference | 5/13/2003 | 5/13/2003 | 5/13/2003 | P | DONE |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 5/13/2003 at 7:50:37 AM. Contact: ###-####.
|
Electrical Rough-In | 5/7/2003 | 5/8/2003 | 5/8/2003 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 5/7/2003 at 4:33:34 PM. Contact: ###-####. conf with contractor 5/8/2003 4:50:12 PM
|
Electrical Rough-In | 1/6/2003 | 1/7/2003 | 1/7/2003 | A | PART |
Pat Lass
|
|
|
partial soffit ###-####
|
Permanent Service | 12/11/2002 | 12/11/2002 | 12/11/2002 | P | PASS |
Pat Lass
|
|
|
rex; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
P/S U/G N Ok 12/11/2002 1:23:57 PM
|