Permit Information
Permit NumberELE02-03651
StatusFinaled
Name BENCHMARK ELECTRIC CO
Site Address 8160 W OVERLAND RD
Project NameULTRA TOUCH CAR WASH
Customer Number 
ePlanReview 
Description
11/22/02/ultra touch carwash/electricl wiring & fixtures for remodeling/initial cert of value $63,900/mls 5-15-03 FINAL ADDITIONAL VALUE $ 88,575.00
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/26/20033/27/20033/27/2003APASS
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok card signed
3/27/2003 10:57:44 AM
Final3/25/20033/25/20033/25/2003PPART
DetailsJack Frank
be sure and check if 120-208 volt panel has been changed, it needs to be a 277-480 volt
Final3/17/20033/17/20033/17/2003ANR
DetailsJack Frank
ttemp occupancy not ready checked out most of job
Permanent Service3/13/20033/17/20033/17/2003ACANC
DetailsJack Frank
Temporary occupancy inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs needs final not p/s see added final 3/17/2003 9:13:04 AM
Electrical Rough-In3/13/20033/14/20033/14/2003AFAIL
DetailsMike Kinnear
Ceiling inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs fail low voltage needs to be totally cleaned up & straping for flex conduit 1ft from box (show window light outlets) 3/14/2003 9:43:44 AM
Electrical Rough-In3/14/20033/14/20033/14/2003PPASS
DetailsJim Schmer
Ceiling inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs
Final3/13/20033/14/20033/13/2003ACANC
DetailsJack Frank
Ceiling inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs Inspection cancelled from web by: Kathy Briggs
Permanent Service2/20/20032/21/20032/21/2003ANR
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs conference ok 2/21/2003 8:49:01 AM
Permanent Service2/21/20032/21/20032/21/2003PPASS
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs p/s u/g new ok 2/21/2003 2:32:47 PM
Electrical Rough-In2/13/20032/14/20032/14/2003APART
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs walls ceiling brack rm and rest rm, also walls store cash wrap area, and display area 2/14/2003 11:10:37 AM
Electrical Rough-In2/3/20032/4/20032/4/2003APASS
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs walls and ceiling 2/4/2003 10:15:01 AM
Electrical Rough-In2/3/20032/3/20032/3/2003PFAIL
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs cor. posted met contactor, 300.4 nail plates and 11/4 inches 2/3/2003 1:45:29 PM
Electrical Rough-In1/7/20031/8/20031/8/2003APART
DetailsJack Frank
Scheduled by a contractor via Hello! on 01/07/2003 at 16:36:18. Contact: ###-####. 1 inch u/g run for detail area 1/8/2003 11:24:31 AM
Electrical Rough-In1/7/20031/7/20031/7/2003PPART
DetailsJack Frank
Scheduled by a contractor via Hello! on 01/07/2003 at 07:57:45. Contact: ###-####. partial u/g ok 1/7/2003 6:34:42 PM
Electrical Rough-In1/6/20031/6/20031/6/2003PPART
DetailsPat Lass
Scheduled by a contractor via Hello! on 01/06/2003 at 09:22:26. Contact: ###-####.
south side trench ok 1/6/2003 1:44:03 PM
Electrical Rough-In12/27/200212/30/200212/30/2002APART
DetailsJack Frank
Scheduled by a contractor via Hello! on 12/27/2002 at 12:55:33. Contact: ###-####. ok u/g was done 12/27/02 12/30/2002 11:46:49 AM
Electrical Rough-In12/27/200212/27/200212/27/2002PPART
DetailsJack Frank
r/i for u/g ok $42.00 reinspection fee due per J Schmer contractor does not call for inspection , he calls inspector for inspections , this has happened 3 times 12/27/2002 4:58:01 PM
Electrical Rough-In12/26/200212/27/200212/27/2002AFAIL
DetailsJack Frank
dick; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung done it 12/26/02 in the pm 12/27/2002 1:44:27 PM
Electrical Rough-In12/26/200212/26/200212/26/2002PFAIL
DetailsJack Frank
u/g exposed for inspection met with contractor found conduits with over 360 degrees of bends
Electrical Rough-In12/24/200212/26/200212/26/2002AFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 12/24/2002 at 10:16:19. Contact: ###-####. cor. posted called u/g covered before inspection U A C 305.1 12/26/2002 11:16:33 AM
Electrical Rough-In11/22/200211/22/200211/22/2002PPART
DetailsJack Frank
Scheduled by a contractor via Hello! on 11/22/2002 at 08:52:14. Contact: ###-####. concrete encased electrode ok for cover only 11/22/2002 11:39:56 AM