Final | 10/7/2003 | 10/8/2003 | 10/8/2003 | A | PASS |
Jack Frank
|
|
|
aaron; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 10/8/2003 9:42:36 AM
|
Final | 10/6/2003 | 10/7/2003 | 10/7/2003 | A | FAIL |
Jack Frank
|
|
|
homeowner home between 9 & 11 please call at ###-####; Phone #: ###-#### Internet Inspection Request from: Andy Rose needs type s fuses and adaptors, grd receptacle in pantry install plates 10/7/2003 9:21:19 AM
|
Electrical Rough-In | 11/27/2002 | 11/29/2002 | 11/29/2002 | A | PASS |
Jack Frank
|
|
|
###-#### ok 11/29/2002 10:48:41 AM
|
Electrical Rough-In | 11/26/2002 | 11/27/2002 | 11/27/2002 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Amy Lawson cor. posted called 210.52(A&B) needs reuired outlets and small appliance branch circuit for new dinning and pantry area 314.16 cutin box, 300.4 nail and 11/4 , 110.12(A) replace plastic boxes with unused KOs, all make up shall be complete 11/27/2002 11:49:57 AM
|