Temporary Service | 12/10/2002 | 12/11/2002 | 12/11/2002 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/10/2002 at 15:06:33. Contact: ###-####.
t/s u/g new ok 12/11/2002 11:01:09 AM
|
Temporary Service | 12/9/2002 | 12/10/2002 | 12/10/2002 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/09/2002 at 11:47:18. Contact: ###-####. cor. ,and $42.00 REINSPECTION FEE DUE POSTED CALLED 250.30 GRD XFORMER, 200.6AND REMOVE NUETRAL PRIMARY SIDE OF XFORMER 12/10/2002 12:51:58 PM
|
Temporary Service | 11/27/2002 | 11/29/2002 | 11/29/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### kathy 11/29/2002 12:22:06 PM cor. posted called left message 250.119, 250.64 (B) protect #8 grd, 406.8(B)(1) in use covers, 110.3 (A) ringed wire 110.12 (C) clean foreign material from x former, 110.14(A) tighten all nuts bolts and lugs, 450.11 name plate and marking for x former, 450. 22 xformer shall be wheather proof 11/29/2002 1:50:02 PM
|