Temporary Service | 12/9/2002 | 12/10/2002 | 12/10/2002 | A | PASS |
Pat Lass
|
|
|
###-####
T/S U/G Ok 12/10/2002 9:27:53 AM
|
Temporary Service | 12/3/2002 | 12/4/2002 | 12/4/2002 | A | FAIL |
Pat Lass
|
|
|
###-####
408.21 Grounded Conductor Terminations.
Each grounded conductor shall terminate within the panelboard in an individual terminal that is not also used for another conductor.
406.8 Receptacles in Damp or Wet Locations.
(B) Wet Locations.
(1) 15- and 20-Ampere Outdoor Receptacles. 15- and 20-ampere, 125- and 250-volt receptacles installed outdoors in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted.
527.6 Ground-Fault Protection for Personnel.
(B) Use of Other Outlets. Receptacles other than 125-volt, single-phase, 15-, 20-, and 30-ampere receptacles shall have protection in accordance with (1) or, the assured equipment grounding conductor program in accordance with (2).
(1) GFCI Protection. Ground-fault circuit interrupter protection for personnel.
12/4/2002 10:55:02 AM
|