Permit Information
Permit NumberELE02-03728
StatusFinaled
Name GOUL ASHLEY
Site Address 405 E HIGHLAND VIEW DR
Project NameHillside
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Temporary Service12/9/200212/10/200212/10/2002APASS
DetailsPat Lass
###-####
T/S U/G Ok 12/10/2002 9:27:53 AM
Temporary Service12/3/200212/4/200212/4/2002AFAIL
DetailsPat Lass
###-####
408.21 Grounded Conductor Terminations.
Each grounded conductor shall terminate within the panelboard in an individual terminal that is not also used for another conductor.

406.8 Receptacles in Damp or Wet Locations.
(B) Wet Locations.
(1) 15- and 20-Ampere Outdoor Receptacles. 15- and 20-ampere, 125- and 250-volt receptacles installed outdoors in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted.

527.6 Ground-Fault Protection for Personnel.
(B) Use of Other Outlets. Receptacles other than 125-volt, single-phase, 15-, 20-, and 30-ampere receptacles shall have protection in accordance with (1) or, the assured equipment grounding conductor program in accordance with (2).
(1) GFCI Protection. Ground-fault circuit interrupter protection for personnel.
12/4/2002 10:55:02 AM