Final | 7/15/2003 | 7/15/2003 | 7/15/2003 | P | PASS |
Jack Frank
|
|
|
DENNIS; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 7/15/2003 3:05:28 PM
|
ELE-Request for Extension | 7/7/2003 | 7/7/2003 | 7/7/2003 | P | PART |
Jack Frank
|
|
|
###-#### bob called no answer, ok for extention 7/7/2003 4:50:34 PM
|
Rough-In Permanent Service | 12/18/2002 | 12/19/2002 | 12/19/2002 | A | PASS |
Jack Frank
|
|
|
DENNIS ###-#### r/i ok still needs to change out 3 boxes for wire fill basement bed rm
p/s o/h new ok 12/19/2002 11:55:43 AM
|
Rough-In Permanent Service | 12/16/2002 | 12/17/2002 | 12/17/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### dennis cor. posted called 314.43 outside boxes, 314.16, 2150.148, kit 3gang, 300.4 nail plates and 11/4, 250.24 terminate GEC at neutral bus not can, 300.14 needs 6" for make up rquip grds 12/17/2002 2:20:42 PM
|