Final | 4/8/2003 | 4/9/2003 | 4/9/2003 | P | PASS |
Jack Frank
|
|
|
joe; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie survey posted 210.70(C), 210.63 a/c in attic 4/9/2003 2:34:53 PM
|
Electrical Rough-In | 3/26/2003 | 3/26/2003 | 3/26/2003 | P | PART |
Pat Lass
|
|
|
###-####
ceiling ok except exit lights and large "J" box
grounding 3/26/2003 12:32:52 PM
|
Permanent Service | 3/18/2003 | 3/19/2003 | 3/19/2003 | P | PASS |
Jack Frank
|
|
|
###-#### p/s u/g new ok 3/19/2003 12:45:09 PM
|
Electrical Rough-In | 3/18/2003 | 3/18/2003 | 3/18/2003 | P | PART |
Jack Frank
|
|
|
contractor called conference ok needs gas line removed from below p/s, shall ID #6 or smaller neutral, and install jumpers to bond bushing, contractor will install PVC for G E C
|
Electrical Rough-In | 2/11/2003 | 2/11/2003 | 2/11/2003 | P | PART |
Jack Frank
|
|
|
###-#### joe walls up and down stairs ok no downstairs ceiling needs to uncover u/g covered before inspection front 2/11/2003 12:47:03 PM
|
Electrical Rough-In | 2/7/2003 | 2/10/2003 | 2/10/2003 | A | FAIL |
Jack Frank
|
|
|
###-#### upstairs ceiling ok only cor posted for walls up and down 300.4 nail plates and 11/4 110.26 (F)(1), 230.7 330.30 (C), 358.26 314.3 or 110.3(B) 2/10/2003 11:39:10 AM
|
Electrical Rough-In | 2/6/2003 | 2/6/2003 | 2/6/2003 | P | PASS |
Tim McCullough
|
|
|
###-#### Joe
ri/ok all walls 2/6/2003 4:19:41 PM
|
Permanent Service | 12/20/2002 | 12/23/2002 | 12/23/2002 | A | NR |
Jack Frank
|
|
|
donny; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie no p/s ready , u/g shall be 18" below dirt where it is inside building called 12/23/2002 12:34:41 PM
|