Final | 12/30/2003 | 12/31/2003 | 12/31/2003 | A | PASS |
Mike Kinnear
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok final per. occ. 12/31/2003 9:07:25 AM
|
Final | 12/30/2003 | 12/30/2003 | 12/30/2003 | P | FAIL |
William E Thomas
|
|
|
Jessie; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
final insp ok for this permit.
there is no permit for any of the work being done with regards to the future air conditioning units in each of the elevator landings in the building.
must see a permit for this work to final off the building. 12/30/2003 2:54:05 PM
|
ELE-Aging Inspection | 12/1/2003 | 12/1/2003 | 12/1/2003 | | NR |
Mike Kinnear
|
|
|
suc 12/1/2003 7:37:46 AM
|
Final | 9/30/2003 | 10/1/2003 | 10/1/2003 | A | PART |
Mike Kinnear
|
|
|
jesse ; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok te3mp occ. note landscaping for ext & court areas ,pent house conduits, platforms for conduits upstairs & downstairs all need to be completed for final. 10/1/2003 10:13:19 AM
|
Final | 9/29/2003 | 9/30/2003 | 9/30/2003 | P | PART |
Mike Kinnear
|
|
|
jessie ###-#### ok cover landscape conduit part 9/30/2003 4:25:10 PM
|
Final | 9/26/2003 | 9/29/2003 | 9/29/2003 | A | PART |
Mike Kinnear
|
|
|
jessie; Phone #: ###-#### Internet Inspection Request from: Darla Downs front landscaping lighting 9/29/2003 9:09:58 AM
|
Electrical Rough-In | 9/25/2003 | 9/26/2003 | 9/26/2003 | A | PART |
Mike Kinnear
|
|
|
jessie; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok cover part under ground in plamters 9/26/2003 10:13:25 AM
|
Electrical Rough-In | 9/26/2003 | 9/26/2003 | 9/26/2003 | P | PASS |
Mike Kinnear
|
|
|
jessie; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok cover under ground front landscape area 9/26/2003 4:04:00 PM
|
Electrical Rough-In | 9/16/2003 | 9/16/2003 | 9/16/2003 | P | PASS |
Jack Frank
|
|
|
jessie celing
; Phone #: ###-#### Internet Inspection Request from: Darla Downs halls and lobby all 4 floors print hi lighted and dated 9/16/2003 4:33:20 PM
|
Electrical Rough-In | 9/10/2003 | 9/11/2003 | 9/11/2003 | P | PART |
Mike Kinnear
|
|
|
jesse//ceiling cover; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ceiling not ready ok cover part ri ok final part rms marked on print 9/11/2003 12:38:20 PM
|
Electrical Rough-In | 9/9/2003 | 9/10/2003 | 9/10/2003 | A | PART |
Mike Kinnear
|
|
|
JESSE; Phone #: ###-#### Internet Inspection Request from: Annette Moore part final 3rd floor 9/10/2003 9:46:50 AM
|
Final | 9/9/2003 | 9/9/2003 | 9/9/2003 | P | PART |
Pat Lass
|
|
|
JESSE *PARTIAL; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
ANOP 9/9/2003 5:05:44 PM
|
Electrical Rough-In | 9/8/2003 | 9/8/2003 | 9/8/2003 | P | PART |
Pat Lass
|
|
|
JESSE *PARTIAL; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
|
Final | 9/3/2003 | 9/3/2003 | 9/3/2003 | P | PART |
Mike Kinnear
|
|
|
jesse partial final; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok final part 3rd & 4th floor marked on print 9/3/2003 2:29:22 PM
|
Final | 9/2/2003 | 9/2/2003 | 9/2/2003 | P | PART |
Pat Lass
|
|
|
###-#### jesse
ANOP 9/2/2003 3:26:00 PM
|
Final | 8/27/2003 | 8/28/2003 | 8/28/2003 | P | PART |
Pat Lass
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
Final | 8/27/2003 | 8/28/2003 | 8/28/2003 | P | PART |
Pat Lass
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
Final | 8/26/2003 | 8/26/2003 | 8/26/2003 | P | FAIL |
Pat Lass
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
remove furniture from room for inspection
reinspection fee due 8/26/2003 2:56:07 PM
|
Final | 8/25/2003 | 8/25/2003 | 8/25/2003 | P | PART |
Pat Lass
|
|
|
JESSIE ( PARTIAL FINAL ) ; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
Electrical Rough-In | 8/6/2003 | 8/6/2003 | 8/6/2003 | P | PART |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
ANOP 8/6/2003 3:17:55 PM
|
Electrical Rough-In | 7/29/2003 | 7/30/2003 | 7/30/2003 | P | PART |
Mike Kinnear
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok cover chase 2nd & 3rd floors 7/30/2003 4:11:39 PM
|
Electrical Rough-In | 7/22/2003 | 7/23/2003 | 7/23/2003 | A | FAIL |
Pat Lass
|
|
|
JESSEE; Phone #: ###-#### Internet Inspection Request from: Dixie Fellows
size of access for motor 7/23/2003 1:33:26 PM
|
Electrical Rough-In | 7/14/2003 | 7/15/2003 | 7/15/2003 | A | PART |
Pat Lass
|
|
|
JESSIE; Phone #: ###-#### Internet Inspection Request from: Dixie Fellows
anop 7/15/2003 8:58:37 AM
|
Electrical Rough-In | 7/14/2003 | 7/14/2003 | 7/14/2003 | P | NH |
Pat Lass
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Electrical Rough-In | 7/10/2003 | 7/11/2003 | 7/11/2003 | P | PASS |
Jim Schmer
|
|
|
bud ceiling inspection; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ceiling in hall, east end only, temp. only 7/11/2003 10:56:21 AM
|
Electrical Rough-In | 7/9/2003 | 7/10/2003 | 7/10/2003 | A | PASS |
Jim Schmer
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Final | 7/2/2003 | 7/3/2003 | 7/3/2003 | A | PASS |
Jim Schmer
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ground floor, internet, laundry & exersice rooms. 7/3/2003 8:21:10 AM
|
Electrical Rough-In | 6/30/2003 | 7/1/2003 | 7/1/2003 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 6/30/2003 at 11:50:50 AM. Contact: ###-####.
ANOP 7/1/2003 10:37:21 AM
|
Rough-In Permanent Service | 6/25/2003 | 6/26/2003 | 6/26/2003 | A | PART |
Pat Lass
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Annette Moore
anop
P/S U/G N Ok 6/26/2003 10:52:13 AM
|
Electrical Rough-In | 6/23/2003 | 6/24/2003 | 6/24/2003 | A | PART |
Pat Lass
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
4th floor south east corner 6/24/2003 10:43:01 AM
|
Electrical Rough-In | 6/19/2003 | 6/19/2003 | 6/19/2003 | P | PART |
Pat Lass
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Annette Moore
walls in remodle ok 6/19/2003 4:13:10 PM
|
Electrical Rough-In | 6/12/2003 | 6/13/2003 | 6/13/2003 | A | PASS |
Jim Schmer
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 10 units 2nd and 4th floor 6/13/2003 8:24:57 AM
|
Permanent Service | 6/11/2003 | 6/11/2003 | 6/11/2003 | P | PASS |
Pat Lass
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
P/S U/G N Ok 6/11/2003 2:34:43 PM
|
Electrical Rough-In | 6/6/2003 | 6/6/2003 | 6/6/2003 | P | PART |
Pat Lass
|
|
|
JESSIE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
2nd floor n/w corner 10 units 6/6/2003 2:38:31 PM
|
Electrical Rough-In | 6/2/2003 | 6/3/2003 | 6/3/2003 | A | PART |
Mike Kinnear
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok cover rms 117, 120,124,125,126,128,130,132,134,131,&133 6/3/2003 10:43:21 AM
|
Electrical Rough-In | 6/2/2003 | 6/2/2003 | 6/2/2003 | P | NR |
Pat Lass
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
Electrical Rough-In | 5/29/2003 | 5/30/2003 | 5/30/2003 | A | PART |
Mike Kinnear
|
|
|
jesse ; Phone #: ###-#### Internet Inspection Request from: Annette Moore 5/30/2003 10:06:21 AM ok cover rooms 110, 111, 112, 114, 115, 116, 118, & 122 5/30/2003 11:14:23 AM
|
Electrical Rough-In | 5/23/2003 | 5/27/2003 | 5/27/2003 | A | PART |
Pat Lass
|
|
|
###-####
ANOP 5/27/2003 11:09:15 AM
|
Electrical Rough-In | 5/6/2003 | 5/6/2003 | 5/6/2003 | P | PART |
Mike Kinnear
|
|
|
JESSIE; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok cover ri second floor east half survey plan A2 kitch wall needs outlet 4ft wall 5/6/2003 3:34:46 PM
|
Electrical Rough-In | 4/16/2003 | 4/16/2003 | 4/16/2003 | P | PART |
Pat Lass
|
|
|
jesse; Phone #: ###-#### Internet Inspection Request from: Annette Moore
anop 4/16/2003 4:09:04 PM
|
Electrical Rough-In | 4/15/2003 | 4/15/2003 | 4/15/2003 | P | PART |
Pat Lass
|
|
|
JESSIE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
anop 4/15/2003 4:43:53 PM
|
Electrical Rough-In | 4/11/2003 | 4/14/2003 | 4/14/2003 | A | NR |
Pat Lass
|
|
|
###-#### jesse
|
Conference | 3/20/2003 | 3/21/2003 | 3/21/2003 | A | PASS |
Pat Lass
|
|
|
JESSIE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
Electrical Rough-In | 1/15/2003 | 1/15/2003 | 1/15/2003 | P | PASS |
Jim Schmer
|
|
|
groundwork- jesse; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie grd to ufer 1/15/2003 11:59:11 AM
|