Final | 3/19/2003 | 3/20/2003 | 3/20/2003 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 3/19/2003 at 2:06:11 PM. Contact: ###-####. ok 3/20/2003 10:29:03 AM
|
Rough-In Permanent Service | 1/22/2003 | 1/23/2003 | 1/23/2003 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 01/22/2003 at 14:45:52. Contact: ###-####. cor. made r/i ok
p/s u/g new ok 1/22/2003 4:13:46 PM
|
Rough-In Permanent Service | 1/22/2003 | 1/22/2003 | 1/22/2003 | P | FAIL |
Jack Frank
|
|
|
###-####- jim cor. posted called 210.52(B)&210.23(A) exception remove vacuum outlet from kit. circuit 250.148 (A) grd box upstairs hallway, 334.30&314.17(C) staple romex at all boxes, note install mudring switch dinning rm 1/22/2003 2:00:51 PM
|