Permit NumberELE03-00815
StatusFinaled
Name CONTROL WEST ELECTRIC INC
Site Address 11603 W FAIRVIEW AVE
Project NameCLOVERDALE PLUMBING
Customer Number 
ePlanReview 
Description
New service and complete rewire per initial cert of value $7,500.00///Final cert of value $12,830///3/14/05 BAS
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/10/20052/10/20052/10/2005PPASS
DetailsBob Reichert
dan///please call at least a half hour prior to inspection so he can meet ya there; Phone #: ###-#### Internet Inspection Request from: Barbara Moore told contr he had to add strap to service cnd. ok to final 2/10/2005 4:26:29 PM
ELE-Aging Inspection10/5/200410/5/200410/5/2004 DONE
DetailsWilliam E Thomas
suc 10/5/2004 3:41:11 PM
ELE-Aging Inspection7/26/20047/26/20047/26/2004 DONE
DetailsJoe Ray
work in progress 7/27/2004 8:03:37 AM
ELE-Aging Inspection5/12/20045/12/20045/12/2004 NR
DetailsJoe Ray
still under contr 5/12/2004 3:37:35 PM
Rough-In Permanent Service2/11/20042/11/20042/11/2004PPASS
DetailsJack Frank
DAN (please call for access); Phone #: ###-#### Internet Inspection Request from: Annette Moore r/i ok
p/s u/g new ok 2/11/2004 12:46:13 PM
Rough-In Permanent Service2/10/20042/10/20042/10/2004PCANC
DetailsJack Frank
dan-call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie not ready called Dan he said he will reschedule 2/10/2004 12:48:30 PM
Rough-In Permanent Service2/9/20042/9/20042/9/2004PFAIL
DetailsJack Frank
dan; Phone #: ###-#### Internet Inspection Request from: Annette Moore all corrections not made, and new ones created 314.28 jbox back back of p/s 110.3(B) no metallic nipples allowed in plastic boxes, where is grd or bond to water system?, 11/2 flex at sub panel not in fitting and needs proper radius of bend COW called 2/9/2004 2:00:25 PM
Electrical Rough-In10/6/200310/6/200310/6/2003PFAIL
DetailsJoe Ray
dan; Phone #: ###-#### Internet Inspection Request from: Annette Moore corrections not made 10/6/2003 1:45:14 PM
Electrical Rough-In9/30/200310/1/200310/1/2003AFAIL
DetailsJoe Ray
Scheduled by a contractor via Hello! on 9/30/2003 at 11:54:00 AM. Contact: ###-####. bond metal rings/protect ent with in a 1 1/4/run to panel shall be in conduit 10/1/2003 10:37:19 AM
Electrical Rough-In3/19/20033/20/20033/20/2003APASS
DetailsJoe Ray
DAN; Phone #: ###-#### Internet Inspection Request from: Annette Moore under ground ok for cover 3/20/2003 10:07:46 AM