Final | 5/2/2003 | 5/2/2003 | 5/2/2003 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 5/2/2003 at 10:49:24 AM. Contact: ###-####. ok final corrections made 5/2/2003 2:16:32 PM
|
Final | 4/14/2003 | 4/18/2003 | 4/18/2003 | A | FAIL |
Jack Frank
|
|
|
wayne; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corrections not made called see notes in history 4/18/2003 9:45:36 AM
|
Final | 4/9/2003 | 4/10/2003 | 4/10/2003 | P | NH |
Jack Frank
|
|
|
###-#### called contractor will reschedule 4/10/2003 4:12:52 PM
|
Final | 4/3/2003 | 4/4/2003 | 4/4/2003 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 4/3/2003 at 5:06:32 PM. Contact: ###-####. cor. and $42.00 fee due posted 300.10,230.24(A), 680.26(A)(B),680.22(A)(3), 250.8,250.24 grd servive not sub panel grd or bond as 250.52,or 250.104 states, 110.3 cut sheetrock at sub panel so cover fits properly 4/4/2003 9:58:05 AM
|