ELE-Aging Inspection | 9/22/2003 | 9/22/2003 | 9/22/2003 | | PASS |
Mike Kinnear
|
|
|
finaled by 324 9/22/2003 7:37:01 AM
|
Electrical Rough-In | 7/21/2003 | 7/22/2003 | 7/22/2003 | A | CANC |
Jim Schmer
|
|
|
Scheduled by a contractor via Hello! on 7/21/2003 at 11:56:50 AM. Contact: ###-####. should have been final 7/22/2003 9:16:48 AM
|
Final | 7/22/2003 | 7/22/2003 | 7/22/2003 | A | PASS |
Jim Schmer
|
|
|
|
Final | 7/22/2003 | 7/22/2003 | 7/22/2003 | A | PASS |
Jim Schmer
|
|
|
|
Final | 7/17/2003 | 7/18/2003 | 7/18/2003 | P | FAIL |
Jack Frank
|
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called left message,, 410.15(B) grd light poles at hand hole, ne power to roof top unit recepts, on roof , also they need in use covers, ATM wiring in parking lot bottom of box cut out, high and low voltage togrther in box ? also no permit for signs 7/18/2003 4:26:20 PM
|
Electrical Rough-In | 6/24/2003 | 6/25/2003 | 6/25/2003 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 6/24/2003 at 9:41:17 AM. Contact: ###-####. ok cover drop ceiling only 6/25/2003 3:45:40 PM
|
Permanent Service | 6/24/2003 | 6/25/2003 | 6/25/2003 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 6/24/2003 at 9:42:17 AM. Contact: ###-####. p/s u/g n ok 6/25/2003 2:51:34 PM
|
Electrical Rough-In | 6/10/2003 | 6/12/2003 | 6/12/2003 | A | PASS |
Tim McCullough
|
|
|
Scheduled by a contractor via Hello! on 6/10/2003 at 10:55:58 AM. Contact: ###-####.
trench/ok 6/12/2003 9:46:12 AM
|
Electrical Rough-In | 5/14/2003 | 5/15/2003 | 5/15/2003 | P | PASS |
Tim McCullough
|
|
|
Scheduled by a contractor via Hello! on 5/14/2003 at 3:42:08 PM. Contact: ###-####.
ri walls / hard lid 5/15/2003 1:49:06 PM
|
Electrical Rough-In | 4/25/2003 | 4/28/2003 | 4/28/2003 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 4/25/2003 at 10:06:31 AM. Contact: ###-####.-trench insp ok cover underground conduit 4/28/2003 11:03:06 AM
|
Electrical Rough-In | 4/23/2003 | 4/23/2003 | 4/23/2003 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 4/23/2003 at 9:48:32 AM. Contact: ###-####. TRENCH INSPECTION ok cover part underground conduit 4/23/2003 4:37:18 PM
|
Electrical Rough-In | 4/21/2003 | 4/21/2003 | 4/21/2003 | P | PART |
Mike Kinnear
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok cover under ground conduit part parking area 4/21/2003 5:16:04 PM
|
Electrical Rough-In | 4/17/2003 | 4/18/2003 | 4/18/2003 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 4/17/2003 at 11:24:31 AM. Contact: ###-####. part under ground parking lot conduit 4/18/2003 10:08:35 AM
|
Electrical Rough-In | 4/9/2003 | 4/10/2003 | 4/10/2003 | A | PART |
Mike Kinnear
|
|
|
###-#### under slab inspection ok cover slab conduit 4/10/2003 9:59:30 AM
|