Final | 12/1/2003 | 12/2/2003 | 12/2/2003 | A | PASS |
William E Thomas
|
|
|
Jim; Phone #: ###-####, please call first for acces, thanks. Internet Inspection Request from: Aimee Hughes
final ok 12/2/2003 11:06:09 AM
|
Electrical Rough-In | 5/8/2003 | 5/8/2003 | 5/8/2003 | P | PASS |
Tim McCullough
|
|
|
JIM; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ok/cover 5/8/2003 1:44:44 PM
|
Electrical Rough-In | 5/6/2003 | 5/7/2003 | 5/7/2003 | A | FAIL |
Jack Frank
|
|
|
JIM; Phone #: ###-#### Internet Inspection Request from: Darla Downs PLEASE COME AROUND TO THE BACK OF THE HOUSE TO ENTER cor. posted called left message,210.52(A) needs outlet for wall space between slider and garage door, 300.4 (D) 11/4, 314.43 no screws allowed in non metallic boxes 5/7/2003 10:11:33 AM
|