Electrical Rough-In | 9/29/2003 | 9/29/2003 | 9/29/2003 | P | PASS |
Joe Ray
|
|
|
tim ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
Final | 9/26/2003 | 9/26/2003 | 9/26/2003 | P | FAIL |
Jack Frank
|
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 250.148 grd box at island, 406.4(D) recepts shall be flush with plates, 314.20 needs box extensions where boxes are set back more than 1/4" 210.52(A) outlet more than 6 ft left of bath entry in MBed, 300.5 uf too post light shall be 12" deep needs r/i inspection for trench, post address, need access to garage recepts doors in the way , install all light fixtures entry light 9/26/2003 4:09:34 PM
|
Rough-In Permanent Service | 6/9/2003 | 6/10/2003 | 6/10/2003 | A | PASS |
Joe Ray
|
|
|
Scheduled by a contractor via Hello! on 6/9/2003 at 6:24:52 PM. p/s ug n ok 6/10/2003 8:40:00 AM
|
Electrical Rough-In | 6/9/2003 | 6/9/2003 | 6/9/2003 | P | FAIL |
Joe Ray
|
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Annette Moore box fill/ recpt for ac/recpt for 2 ft wall/cover panel 6/9/2003 2:58:39 PM called no answer 6/9/2003 3:02:38 PM
|