Final | 6/10/2003 | 6/10/2003 | 6/10/2003 | P | PASS |
Jack Frank
|
|
|
henry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 6/10/2003 2:32:15 PM
|
Final | 6/4/2003 | 6/5/2003 | 6/5/2003 | A | NR |
Jack Frank
|
|
|
henry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore needs too terminate GEC at neutral bus, and bond around di electric unions hot and cold water pipes see added p/s 6/5/2003 1:13:36 PM
|
Permanent Service | 6/5/2003 | 6/5/2003 | 6/5/2003 | P | PASS |
Jack Frank
|
|
|
p/s o/h rec. ok
|
Permanent Service | 5/28/2003 | 6/2/2003 | 6/2/2003 | A | FAIL |
Jack Frank
|
|
|
###-#### cor. posted called 250.92(A)(3), 250.66,52(A)(1),104(A)(1) needs #4 G.E.C. for grd or bond too water system, 250.24(A)(1) terminate G.E.C. too neutral bus, 230.24(A) needs 8f over roof , 250.53(B) grd rods shall be 6ft or more apart 6/2/2003 10:34:18 AM
|