Final | 7/1/2003 | 7/2/2003 | 7/2/2003 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/1/2003 at 5:02:46 PM. Contact: ###-####. ok 7/2/2003 8:36:38 AM
|
Electrical Rough-In | 6/25/2003 | 6/26/2003 | 6/26/2003 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/25/2003 at 1:03:19 PM. Contact: ###-####. called cor.not made 6/26/2003 11:32:49 AM
|
Rough-In Permanent Service | 6/23/2003 | 6/24/2003 | 6/24/2003 | A | CANC |
Tim McCullough
|
|
|
###-#### terricanceled 6/24/2003 10:23:16 AM
|
Rough-In Permanent Service | 6/23/2003 | 6/24/2003 | 6/24/2003 | A | FAIL |
Jack Frank
|
|
|
###-#### terri cor. posted called 250.32 (B)(1) isolate grds and neuts garage p/s, 250.104 bond hot and cold at house, 250.53 (D)(2) garage needs 2 grd rods,, also remove grd wire from sub panel in basement 6/24/2003 9:32:47 AM
|