Final | 3/22/2004 | 3/23/2004 | 3/23/2004 | P | PASS |
Pat Lass
|
|
|
rex; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
Final | 3/22/2004 | 3/22/2004 | 3/22/2004 | P | FAIL |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 3/22/2004 at 7:02:47 AM. Contact: ###-####.
408.4 Circuit Directory.
All circuits and circuit modifications shall be legibly identified as to purpose or use on a circuit directory located on the face or inside of the panel door in the case of a panelboard, and at each switch on a switchboard.
210.52 Dwelling Unit Receptacle Outlets.
(B) Small Appliances.
(1) Receptacle Outlets Served. In the kitchen, pantry, breakfast room, dining room, or similar area of a dwelling unit, the two or more 20-ampere small-appliance branch circuits required by 210.11(C)(1) shall serve all receptacle outlets covered by 210.52(A) and (C) and receptacle outlets for refrigeration equipment.
lights and disposal are on small-appliance circuits ans mismarked in panel 3/22/2004 3:08:16 PM 3/22/2004 3:19:32 PM
|
Electrical Rough-In | 9/22/2003 | 9/23/2003 | 9/23/2003 | A | PASS |
Pat Lass
|
|
|
###-####. Scheduled by a contractor via Hello! on 9/22/2003 at 2:02:20 PM. Contact: ###-####. 9/23/2003 7:14:37 AM
|
Permanent Service | 9/23/2003 | 9/23/2003 | 9/23/2003 | A | PASS |
Pat Lass
|
|
|
P/S U/G N Ok
|